EasyManua.ls Logo

Eaton Cutler-Hammer MP-3000 - Page 120

Eaton Cutler-Hammer MP-3000
123 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 120 I.L. 17562
PR 0.3 Effective 8/99
(emptied) below the user-set
I2T alarm level. This time
depends on motor
nameplate values entered
as setpoints.
in supply currents or
voltages causing
negative-sequence
heating.
Check for abnormal
system voltage level.
Check for cooling air
blockage or abnormal
ambient.
INC SEQ INCOMPLETE
SEQUENCE TRIP
Discrete input 2 has been
set for the incomplete
sequence timing function
via setpoint P7L1. The 120
Vac feedback signal from
the process or starter,
expected within the user-set
time delay, was not
received in time after the
start or transition.
Also, the discrete input 2
must remain energized
during the run cycle, until
the motor stops. An
interruption over 25 cycles
will cause an incomplete
sequence trip.
Check to be sure this
function has been
intentionally enabled.
Check process
feedback wiring to be
sure 120 Vac signal is
delivered in the
expected time.
Use DI 2 test to
confirm that relay sees
input.
Check setpoint P5L8
against process
feedback time.
Check setpoint P5L9
to be sure correct timing
start point is selected -
start or transition.
If timing from
transition, be sure
transition current and
time settings are correct.
ZSW TRIP ZERO SPEED SWITCH
INPUT FAILED TO BE
FALSE WITHIN 1/2 OF
LOCKED ROTOR TIME,
OR WAS FALSE AT
START.
Discrete input 1 has been
set for zero-speed switch
sensing via setpoint P6L1.
The 120 Vac zero speed
switch contact input was not
present at the moment of
the start; or it did not go
away in one-half of the set
locked rotor or stall time
P1L3. This may be due to a
motor which is unable to
start spinning when it is
energized.
Check to be sure this
function has been
intentionally enabled.
If ZSW trip occurs at
the moment of starting,
check process wiring
and contact to be sure
120 Vac signal is
delivered to DI 1 when
the motor is stopped.
Check to be sure the
motor isn't stalled and
actually begins to spin.
If ZSW trip occurs
after 1/2 the locked rotor
time setting, check to be
sure the contact on the
motor opens and the 120
Vac signal goes away
before this time.
Usually, a zero-speed
switch should open when
the motor has reached
5% to 10% of its normal

Related product manuals