Page 44 I.L. 17562
PR 0.3 Effective 8/99
Page Line Value Complete Help Message Description
OF EVENT"
WT2 XXX WINDING TEMP 2 IN
DEGREES (F OR C) AT TIME
OF EVENT"
WT3 XXX WINDING TEMP 3 IN
DEGREES (F OR C) AT TIME
OF EVENT"
WT4 XXX WINDING TEMP 4 IN
DEGREES (F OR C) AT TIME
OF EVENT"
WT5 XXX WINDING TEMP 5 IN
DEGREES (F OR C) AT TIME
OF EVENT"
WT6 XXX WINDING TEMP 6 IN
DEGREES (F OR C) AT TIME
OF EVENT"
MT1 XXX MOTOR BEARING TEMP 1 IN
DEGREES (F OR C) AT TIME
OF EVENT
MT2 XXX MOTOR BEARING TEMP 2 IN
DEGREES (F OR C) AT TIME
OF EVENT
LT1 XXX LOAD BEARING TEMP 1 IN
DEGREES (F OR C) AT TIME
OF EVENT
LT2 XXX LOAD BEARING TEMP 2 IN
DEGREES (F OR C) AT TIME
OF EVENT
AXT XXX AUXILIARY TEMP IN
DEGREES (F OR C) AT TIME
OF EVENT
LOG
STRT
DETAILED LOG OF THE LAST
4 STARTS
This page contains detailed
information about the last four
motor starts.
START X START NUMBER MOST
RECENT START EQUAL 1
Each of the last 4 starts are
numbered 1 being the most recent
and 4 being the oldest. Press line
up to get the latest start line down
to get the oldest start.
MM/DD/YY DATE OF EVENT The date of start
HH.MM TIME OF EVENT The time of start
IA XXX MAXIMUM PHASE A
CURRENT DURING START
Highest of each phase current in
amps during start
IB XXX MAXIMUM PHASE B
CURRENT DURING START
IC XXX MAXIMUM PHASE C
CURRENT DURING START
IG XXX MAXIMUM GROUND FAULT
CURRENT DURING START
The highest ground fault current in
amps during start
UB XXX MAXIMUM PHASE
UNBALANCE DURING START
The highest percent sequence
current unbalance during start
ITR XXX AVERAGE CURRENT AT TIME
OF TRANSITION IN AMPS
The average current of all three
phases in amps at start transition
TSTI XXX TIME FROM START TO The elapsed time from start to