EasyManua.ls Logo

Eaton Cutler-Hammer MP-3000 - URTD Module Wiring

Eaton Cutler-Hammer MP-3000
123 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 70 I.L. 17562
PR 0.3 Effective 8/99
be connected depend on the setpoint programming of the MP-3000 - there is a long list of
functions which can be assigned to each of these inputs.
The engineer designing the installation should study Sections 5 and 9 to understand and
designate the use, if any, of the discrete contact-sensing inputs. Note that only one use can be
assigned to each input.
CAUTION
The discrete inputs should be energized only from 120 Vac. The MP-3000 terminal 6 is always a
source of 120 Vac, which can be used to wet remote contacts, even when the MP-3000 is
powered from 240 Vac.
The discrete input circuits are totally isolated from the other circuits in the MP-3000, and have
their own common connection, terminal 9. If the 120 Vac discrete contact-wetting source from
terminal 6 is used, tie the discrete input common terminal 9 to the ac supply neutral terminal 7,
as shown in Figure 6.7.
Figure 6.8, lower portion, shows an alternate scheme for using a remote contact wetting source.
The source must be 120 Vac. The contact signal(s) and the remote neutral must be brought to
the MP-3000 discrete inputs. For noise immunity and safety, do not connect the discrete
common terminal 9 to terminal 7 or any other nearby neutral if a remote wetting source is in use.
CAUTION
Beware of large shunt capacitance across contacts or in solid-state relays connected to the MP-
3000 discrete inputs. Charging current through the capacitor could cause a false indication of a
closed contact. Keep total capacitance below 0.05 microfarads.
6.2.5 Analog output wiring - Terminals 24 and 25 provide an isolated source of dc current
between 4 and 20 mA, the exact value indicating an internal MP-3000 measurement. This
current source, if used, is typically connected to a remote panel meter or a programmable logic
controller.
The measurement selection is made via MP-3000 setpoint. Choices include motor current;
stator winding temperature; and fill level of the rotor thermal-model bucket between cool level
and trip level. See setpoint P11L1 in Section 5.
The burden of the connected current loop should be less than 1000 ohms.
6.2.6 URTD Wiring - Connect a source of 120 Vac only to the power terminals of connector J3
on the URTD module. Connect either terminal 16 or terminal 32 (but not both) to a non-current-
carrying safety ground.
Figure 6.7 shows connections between the URTD and the MP-3000. Use either the optical fiber
or the electrical 3-wire connection. It is not necessary to connect both. If both are connected,
the MP-3000 will use data from the optical fiber. It will default to the wired connection only if the
fiber is removed or fails.
NOTE
The optical fiber is the much-preferred method of transmitting temperature data from the URTD
to the MP-3000. It is also easier to install.
Preassembled plastic optical fibers with connectors can be ordered from Cutler-Hammer, or from
any distributor of Hewlett-Packard optical fiber products:

Related product manuals