Connections
Connect DC Power
Your PanelMate unit operates at 24VDC -
15%/+20%. A removable three-position DC power
connector attaches to the unit's connector
receptacle as shown in the diagram below. The DC
input common (-terminal) and the chassis GND
terminal are both internally connected to the
PanelMate chassis.
Use #18 AWG (0.82mm2) copper wire for
power and ground lead connections.
Power conditioning may be required when
the PanelMate unit is installed in areas of
poor power quality.
Note:
Note:
Your PanelMate unit could be damaged if it is
connected to voltages outside the range of 18 to
30VDC. Your PanelMate unit is fully protected
against polarity reversal and will not operate if
input polarity is reversed.
If you are replacing a PanelMate Power Series
1500 unit, check the rating of your existing
24VDC power supply. The PanelMate 1700 unit
requires a power supply rated for 1.5A
operation.
Connection to a Personal Computer
Connection to the Fault Relay
Connection to the Audio Output
Connection to the Security Keyswitch
Executive firmware and PanelMate configurations
are uploaded/downloaded to a PC using the
PanelMate unit's serial port. A download serial
cable is provided with your PanelMate
Configuration software. Refer to your PanelMate
Getting Started Manual for more information.
The fault relay may be wired in normally open or
normally closed configuration. It is a Form C
contact, rated for 2 amps at 120VAC, 2 amps at
230VAC, and 2 amps at 28VDC resistive load.
During normal operation, the fault relay will
energize after entering Run Mode.Whenever the
PanelMate unit detects a communication error or
system failure, the fault relay will be de-energized. It
is also possible to de-energize the fault relay
whenever an alarm condition occurs.You can set
the fault relay to de-energize on alarms by using the
System Parameters Table. Refer to the System
Parameters topic in the Configuration Software
Online Help and in the Configuration Editor User's
Guide for more information.
The Audio Feedback Kit is an optional accessory to
your PanelMate unit.To connect the external 8Ohm
speaker to your PanelMate unit, connect the
speaker to the Audio connector.
The Security Keyswitch connection is provided for
external security/password applications.
+
_
GND