3 Installation
3.5 Control Voltage
EMT6 10/16 MN03407006Z-DE/EN www.eaton.com 51
3.4.1 Terminal capacity
Table 2: Conductor cross-sections of the auxiliary cables
3.5 Control Voltage
EMT6... units can be operated with the following control voltages:
Table 3: Control voltages and voltage safety
6 mm (0.24“)
mm
2
mm
2
AWG mm Nm lb-in
1 x (0.5 - 2.5) 1 x (0.5 - 2.5) 20 - 14 0.8 x 4
0.8 x 5.5
1 x 6
Z2 0.8 - 1.2 7.1 - 10.6
2 x (0.5 - 1.5)
2 x (0.5 - 1.5) 20 - 16 0.8 x 4
0.8 x 5.5
1 x 6
Z2 0.8 - 1.2 7.1 - 10.6
EMT6
EMT6-K
EMT6-DB
EMT6-KDB
EMT6-DBK
EMT62
EMT62-DB
EMT6(230V)
EMT6-DB(230V)
AC control voltage 24 - 240 V, 50 - 400 Hz 230 V, 50/60 Hz
DC Control voltage 24 - 240 V H
AC voltage safety 20.4 - 264 V, 50 - 400 Hz 195.5 - 253 V, 50/60 Hz
DC voltage safety 20.4 - 264 V H