EXTERNAL BYPASS SWITCH INSTALLATION
Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide S 164201403 Rev B
www.eaton.com/powerquality
40
60 Hz 120 Vac Input - 120 Vac Output
Figure 12. FE 4.3–7 kVA UPS with External Bypass Switch
Table 17. Minimum Recommended Circuit Breakers for 120 Vac
Charger 4.3 kVA 5.3 kVA 7 kVA
Standard 40 50 70
10A 45 60 70
20A 50 60 70