EXTERNAL BYPASS SWITCH INSTALLATION
Eaton FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide S 164201403 Rev B
www.eaton.com/powerquality
41
60 Hz 208 Vac or 240 Vac Input - 120/208 Vac or 120/240 Vac Output
For 208 Vac, use only a BBM switch.
Figure 13. FE 4.3–18 kVA UPS with External Bypass Switch
Table 18. Minimum Recommended Circuit Breakers for 208 Vac or 240 Vac
208 Vac 240 Vac
Charger 4.3
kVA
5.3
kVA
7
kVA
10
kVA
12.5
kVA
18
kVA
4.3
kVA
5.3
kVA
7
kVA
10
kVA
12.5
kVA
18
kVA
Standard 25 30 40 60 80 110 20 25 35 50 70 100
10A 25 30 40 70 80 125 20 30 35 60 70 100
20A 30 35 40 70 90 125 25 35 35 60 80 110