Eaton K1650 - K1650 and K6050 Alternator Purge Calibration

Eaton K1650
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
INM MTL 130-0126 Rev 13
5.3.2 K1650 and K6050 alternator purge calibration
Figure 12 - Purge calibration menu options
Calibration
rejected
Measuring Measuring Measuring
Calibration
accepted
Calibration
accepted
Calibration
accepted
Calibration
rejected
Pass Dry Air
###.#% H2
MEAS. When ready
VIEW to exit
EDIT for Air cal.
↑ for CO
cal.
VIEW to exit
2
↓ for H
cal.
2
Pass 100%CO2
###.#%CO2
MEAS. When ready
VIEW to exit
Pass 100%H2
###.#% H2
MEAS. When ready
VIEW to exit
Calibration
error
Reading too high
VIEW to continue
Calibration
error
Reading too high
VIEW to continue
Calibration
error
Offset too high
VIEW to continue
Calibration
error
Reading too low
VIEW to continue
Calibration
error
Reading too low
VIEW to continue
Calibration
error
Offset too low
VIEW to continue
Measureent Mode
.% H
2
H in Air2
 Secs
ViewCal
Calibration
rejected