Page 
12 
If the system is a 4
-
wire system with a neutral current 
sensor, apply the same current as described above 
through one phase of the breaker, returning through the 
neutral sensor, as shown in Fig. 
14-2.The breaker should 
not trip, and the alarm indicator, 
if 
supplied, should not 
operate.Repeat the test on the other two phases. 
If the system is a 3
-
wire system with no neutral current 
sensor, apply the same current as described above 
through any two phases of the breaker, with the connec
- 
tions exactly as shown in Fig. 14
-
3. The breaker should 
not trip, and the alarm indicator, 
if 
supplied, should not 
operate. Repeat the test using the other two combinations 
of breaker phases. 
a 
CAUTION 
FIELDTESTING SHOULD BE USED FOR 
FUNCTIONALTESTING AND NOT FIELD 
CALIBRATION 
OFTHE DIGITRIP RMS 310 GROUND 
FAULTTRIP UNIT. 
ANY TEMPORARY CONNECTION MADE 
FORTHE 
PURPOSE OF CONDUCTING TESTS SHOULD BE 
RESTOREDTO PROPER OPERATING CONDITIONS 
BEFORE 
RETURNINGTHE BREAKERTO SERVICE. 
The results of the test are to be recorded on the test form 
provided with the equipment. 
7.0 
RATING PLUG 
The rating plug, as illustrated in Figure 15, is used to 
establish the continuous ampere rating of the related 
circuit breaker. 
For adjustable rating plugs (Table 1 
-2), the primary 
current carrying conductors used with the breaker must 
be sized to correspond with the maximum setting of the 
rating plug, in accordance with National Electric Code 
requirements. 
The Long Delay protection function of  the trip unit is set at 
the rating plug value 
((,).The  Short Delay and Instanta
- 
neous protection functions are set as a multiple of  In.The 
Ground Fault protection function is independent of 
In. 
Different rating plugs are available (Table 1
-
2) to match 
the desired current rating and type of circuit breaker into 
which the trip unit is to be installed. 
Complete catalog descriptions of all available rating plugs 
are given in the applicable circuit breaker supplementary 
instruction leaflets (see Section 
8.0). 
8.0 REFERENCES 
8.1 Series C L
-
Frame Molded Case Circuit Breakers 
29C105  Frame Instruction Leaflet 
AD 29
-
1 67L 
8.2 Internal Accessories: 
The following types of internal 
accessories, which mount on the trip unit, are available for 
use. The number of the instruction leaflet covering the 
installation of each accessory is shown. 
Typical Time
-
Current Characteristic 
curves for L Frame Breakers 
. 
Alarm (Signal)/Lockout (ASL) Switch 
........... 
I.L. 29C183 
. 
Auxiliary Switch 
........................................... 
I.L. 29C123 
. 
ShuntTrip 
.................................................... 
I.L.29C146 
. 
Low Energy Shunt Trip 
................................ 
I.L. 29C147 
Undervoltage Release Mechanism (Handle 
Reset 
........................................................... 
I.L. 29C170 
Effective 
March 2003
 
I.L. 29C615E
Courtesy of NationalSwitchgear.com