Effective December 2020
20 Eaton www.eaton.com
Eaton SPD Series for mounting external
to electrical distribution equipment
Instruction Manual IM01005031E - rev. 7
Communication setting changes require a reboot of the micro
controller to enable it.
Figure 52. Method of IP allocation
IP Configuration changes require a reboot of the device
To initiate a soft reset from the WebUI, go to the general tab and
click on the down arrow across from reboot or reset device as
shown below.
Figure 53. Select on down arrow
Figure 54. Click on reboot device
Click OK to verify that you want to continue with this operation.
The LEDs on the display will turn off, then back on again to indi-
cate that this command has been implemented.
Figure 55. Confirm reboot
A pop up window opens to confirm the reboot.
Figure 56. Click on reload
5.3.4 Modbus and BACnet access
The PX-SPD supports Modbus TCP/IP and BACnet/IP using the
ethernet port, both are initially disabled. Using Modbus com-
mands, the PX-SPD can be used to read real time parameters,
events and logs from the connected PX-SPD. You will need a
Modbus TCP capable application such as ModScan which act
as the Modbus primary and the SPD is the Modbus secondary.
Refer to Appendix F Modbus register map for details on avail-
able registers and their properties. Refer to Appendix H for the
BACnet register map.
5.3.5 Sensitivity setting
Attention: Eaton does not recommend the customer modify
the sensitivity setting without first contacting Eaton Customer
Support at 1 800 809-2772 or email SPD@eaton.com.
Increasing the sensitivity will reduce the number of low level
transient counts.
5.3.6 How to reset the PX-SPD password
To reset the Power Xpert SPD password through the local dis-
play, the user must first access the concealed menu. To gain
access to the concealed menu return to the home screen, then
press the following buttons in order within 5 seconds: up, up,
down, down, back, back, enter, enter. This will take you to the
local display concealed menu. Follow the screen prompts to
reset the passwords. When this password reset command is
activated the local display and Web UI passwords are reset to
their default values. The Power Xpert SPD Local Display prompts
the user for a 6 digit numeric password to be entered before
being able to enter the settings menu. The Web UI User name
and password returns to default:
User name: admin
Password: Admin*1
5.3.7 End of life disposal
Before disposing of this device go to Device Actions and select
Reset Device to clear logs of any data.

Other manuals for Eaton SPD Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton SPD Series and is the answer not in the manual?

Eaton SPD Series Specifications

General IconGeneral
TypeSurge Protective Device
Voltage Rating120/240V, 208Y/120V, 480Y/277V
Surge Current CapacityUp to 200kA
Modes of ProtectionL-N, L-G, N-G
Operating Frequency50/60Hz
CertificationsUL 1449
SPD TypeType 1, Type 2
Maximum Surge CurrentUp to 200kA
Nominal Discharge Current (In)10kA, 20kA
Short Circuit Current Rating (SCCR)Up to 200kA
Enclosure TypeNEMA 1
MountingPanel Mount
StandardsUL 1449, IEEE C62.41
DiagnosticsVisual Indicators
Remote MonitoringOptional
Maximum Discharge Current (Imax)Up to 200kA