IB131006EN
Page 12
Effective 07/2017
3-5 TOOLS AND ACCESSORIES
Tools and accessories, both standard and optional are
available for use with the circuit breaker element (Figure
3-1).
Spin-Free Levering-In Crank: Used to crank breaker
between TEST and CONNECTED positions (Style
701B601G11).
Standard Levering-In Crank: (Style 701B601G12).
Maintenance Tool: Used to charge closing springs
manually (Style 8064A02G11).
Extension Rails: Permits breaker to be withdrawn from
its compartment (Style 7813C41G03 for VCP-W and
VCPW-SE) and (Style 7813C41G04 for VCPW-ND).
Rail Clamps: Used to secure breaker to extension rails
(Style 6511C83G11 for VCP-W and VCP-SE) and (Style
6511C83G02 for VCPW-ND).
Lifting Yoke: Used to lift breaker (Style 691C607G11 for
VCP-W and VCPW-SE) and (Style 691C607G02 for
VCPW-ND).
Drawout Ramp: Used to insert or withdraw breaker
from lower compartment without portable lifter (Style
1C14163G02 for VCP-W and VCPW-SE) and (Style
1C14163G01 for VCPW-ND).
Portable Lifter: Used to lift breaker to or from extended
rails (Style 1C14504H01).
Docking Transport Dolly: Used to insert or withdraw
breaker from lower compartment without portable lifter or
move breaker from one location to another (Style
6510C71G11 for VCP-W and VCPW-SE) and (Style
6510C71G02 for VCPW-ND).
Electrical Levering-In Device: Used to electrically
move breaker between TEST and CONNECTED
positions (Style 1A30257G01).
Test Jumper: Used to operate breaker electrically while
breaker is on extension rails or transport dolly (Style
6526C23G11 for VCP-W and VCPW-SE) and (Style
1C15331G01 for VCPW-ND).
Test Cabinet: Used to provide power to operate
breaker outside its compartment (Styles 8346A28G21
G23 for VCP-W and VCPW-SE depending upon voltage
requirements) and (Styles 8346A28G41 – 43 for
VCPWND depending upon voltage requirements).
3-6 TYPE VCP-W VACUUM CIRCUIT BREAKER
ELEMENT WEIGHTS (TABLES 3.1 AND 3.2)
Table 3.1 VCP-W ANSI Rated Breaker Weights
Rating Amperes Lbs. (kg)
50VCPW-ND250 1200 345 (157)
50VCP-W250
50VCPW-SE250
1200
2000
3000
350 (159)
410 (186)
525 (238)
50VCP-W350
50VCPW-SE350
1200
2000
3000
460 (209)
490 (222)
525 (238)
75VCP-W500
75VCPW-SE500
1200
2000
3000
375 (170)
410 (186)
525 (238)
150VCP-W500
150VCPW-SE500
1200
2000
3000
350 (159)
410 (186)
525 (238)
150VCP-W750
150VCPW-SE750
1200
2000
3000
350 (159)
410 (186)
525 (238)
150VCP-W1000
150VCPW-SE1000
1200
2000
3000
460 (209)
490 (222)
525 (238)
150VCP-W1500(63)
150VCPW-SE1500(63)
1200
2000
3000
525 (238)
530 (241)
550 (250)
270VCP-W750(16) 600
1200
2000
460 (209)
480 (218)
500 (227)
270 VCP-W1000(22) 600
1200
2000
460 (209)
480 (218)
500 (227)
270 VCP-W1250(25) 600
1200
2000
460 (209)
480 (218)
500 (227)
270 VCP-W1600(32) 1200
2000
545 (245)
560 (252)
270VCP-W2000(40) 1200
2000
545 (245)
560 (252)
Does not include shipping carton