IB131006EN
Page 53
Effective 07/2017
6-11 TROUBLESHOOTING CHART (Continued Next Page)
SYMPTOM INSPECTION AREA PROBABLE DEFECTS
Fails To Close
Closing Springs not charged Control Circuit
• Control Power
(fuse blown or switch off)
Secondary Disconnects
• Motor Cut-off Switch
(Poor or burned contacts,
Lever not operational)
Terminals and connectors
(Poor or burned contacts)
• Motor
(Brushes worn or commutator
segment open)
Mechanism
• Pawls
(Slipping or Broken)
Ratchet Wheel
(Teeth worn or broken)
• Cam Shaft Assembly
(Sluggish or jammed)
Oscillator
(Reset spring off or broken)
Closing Spring charged but
breaker does not close
No Closing Sound
(Close Coil does
not pick up)
• Control Power
(Fuse blown or switch off)
Secondary
Disconnects
Anti-Pump Relay
(Y relay N. C. contact open or
burned or relay picks up)
Close Coil
(Open or burned)
Latch Check Switch
(Contact open-bad switch or
trip bar not reset)
Auxiliary Switch
(b contact open or burned)
• Motor Cut-off
(Contacts open or burned)
Trip Coil Assembly
(Clapper fails to reset)
Courtesy of NationalSwitchgear.com