16 Digital output module XN-322-12DO-P17
16.3 Wiring topic
101 XN300 slice modules 02/24 MN050002EN Eaton.com
16.3 Wiring topic
Four digital outputs can be wired to each of the connectors X1, X2 and X3.
16.3.1 Connecting the power supply
The cross-sectional area of the +24 V cables used to supply power must be
sized for the maximum output current drawn by each group.
It is impermissible to apply a voltage, at any output, that exceeds the supply
voltage by more than 0.7 V.
16.3.2 Connecting EN 61131-2 short-circuit proof digital outputs
The outputs are able to drive twice their rated operational current briefly
when driving loads with higher inrush currents.
The outputs can be switched off by groups by using the corresponding group
power supplies.
16.3.3 Wiring digital outputs
Figure 64: Wiring example
X1
1
2
3
4
X2
5
6
7
8
X3
9
10
11
12
X4
+1
+2
+3
0V
12DO
P17
S
U
+24 V X1
+24 V X2
+24 V X3