22 Analog input module XN-322-4AI-PTNI
22.4 Technical specifications
155 XN300 slice modules 02/24 MN050002EN Eaton.com
22.4 Technical specifications
22.4.1 Specifications for analog resistance / temperature inputs
22.4.2 Measuring ranges for resistance inputs
The values are represented as a decimal value in ohms with one decimal
place (in 1 / 10 ohm).
Number of analog input channels 4
A-D converter resolution 16 bits
Configurable parameters Pt100, Pt200, Pt500, Pt1000,
NI100, NI1000,
KTY11-62, KTY81-110, KTY81-120,
KTY81-150, KTY81-121, KTY81-122
KTY84-130, KT84-150
Typical measuring current < 300 A
Reading update
4 ms
Input resistance
> 10 M
Input filter
Built-in 10 kHz, second-order low-pass filter
parameterizable Yes
Cumulative error ±0.3% of full scale value
Sensor connection cable resistance max. 100
Isolation
Input vs. Backplane 500 V
eff
status display LEDs green, yellow
Catalog
Number
Resistance range
1 0 ... 250
2 0 ... 500
3
0 ... 1000
4
0 ... 2500
5 0 ... 5000