22 Analog input module XN-322-4AI-PTNI
22.7 Memory layout
XN300 slice modules 02/24 MN050002EN Eaton.com 160
0x5070 0x8xx6
SUB 01
USINT SensorSelectionAI1 0: Pt100 -200 …+150°C 0x0107
1: Pt100 -200 … +850°C
0x5071 0x8xx6#
SUB 02
USINT SensorSelectionAI2 2: Pt200 -200 … +150°C 0x0108
3: Pt200 -200 … +850°C
0x5072 0x8xx6
SUB 03
USINT SensorSelectionAI3 4: Pt500 -200 … +150°C 0x0109
5: Pt500 -200 … +850°C
0x5073 0x8xx6
SUB 04
USINT SensorSelectionAI4 6: Pt1000 -200 … +150°C 0x010A
7: Pt1000 -200 … +850°C
8: NI100 -60 … +150°C
9: NI100 -60 … +250°C
10: NI1000 -60 … +150°C
11: NI1000 -60 … +250°C
12: R 0 … 250
13: R 0 … 500
14: R 0 … 1000
15: R 0 …2500
16: R 0 … 5000
17: KTY11-62 -50 … +150°C
18: KTY81-110 -55 … +150°C
19: KTY81-120 -55 … +150°C
20: KTY81-121 -55 … +150°C
21: KTY81-122 -55 …+150°C
22: KTY81-150 -55 …+150°C
23 KTY84-130 -40 …+300°C
24 KTY84-150 -40 …+300°C
25 Pt100 -200 …+150°C
26-255 reserved
0x5074 0x8xxC
SUB 02
USINT ChannelMeasuring-
Configuration
Bit 0 1: MeasuringConfig_AI1_As_3Wire 0x010B
Bit 1 1: MeasuringConfig_AI2_As_3Wire
Bit 2 1: MeasuringConfig_AI3_As_3Wire
Bit 3 1: MeasuringConfig_AI4_As_3Wire
Bit 4-15 reserved
CAN
Object
Index
Default
CAN
Mapping
EtherCAT
ObjectIn
dex
Size
(byte)
Local I/O
description
Local I/O
addresses