27 Analog output module XN-322-4AO-UI
27.3 Wiring topic
203 XN300 slice modules 02/24 MN050002EN Eaton.com
27.3 Wiring topic
One analog outputs can be wired to each of the four X1 to X4 connectors.
Figure 110: Connection diagram for analog outputs
The PLC configuration tool can be used to define whether the outputs will be
used as analog voltage outputs or as analog current outputs – please refer to
Section “ OutputChannelCong”, page 206.
27.4 Technical data for analog voltage outputs
X5
24 24
F1
X1
1U
1I
PE
24 V
0 V
U
-+
+
-
X2
2U
2I
U
-+
+
-
X3
3U
3I
U
-+
+
-
X4
4U
4I
U
-+
+
-
0V
0V
Number of analog channels 4
Measuring range V -10 … +10 0 … +10
Measured value -30,000 … +30,000 0… +60,000
Over Range Measuring range V
-10 ,8… +10.8 0 … +10,8
Over Range Measured value
-32,400… +32,400 0… +64,800
D-A converter
16 Bit
Resolution mV/LSB
0.3 0.15
Internal module refresh time s 100
Maximum output current per channel mA
2
Max. capacitive load nF 100
Short circuit protection yes (max. 1 minute)
Accuracy
Cumulative error % ± 0.04