EasyManua.ls Logo

Eaton XN300 - Page 325

Eaton XN300
347 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38 XN-322-2SI-RS serial interface specialty module
38.6 Memory layout
321 XN300 slice modules 02/24 MN050002EN Eaton.com
0x3205 2 ControlRb485
Reading back
Status485
Byte 0
Modem
Control-
Register
Bit 0 Data Terminal
Ready
0x0282
Bit 1 Request to Send
Bit 2 (fix) 1: RS485
mode
Bit 3 reserved
Bit 4 reserved
Bit 5 1: Echo disable
(default)
Bit 6 reserved
Bit 7 reserved
Byte 1
Line
Control
Register
Bit 0-1
00
01
10
11
Data word length
0: 5 Bit
1: 6 Bit
2: 7 Bit
3: 8 Bit
Bit 2
Number of
stop bits
0:
1:
1 stop bit,
1.5 stop bits for 5-
bit data word
length
2 stop bits for 6-
bit, 7-bit, 8-bit
data word length
Bit 3 Parity Enable
0: No parity
1: Parity
Bit 4 Even Parity Select
0: Odd
1: Even
Bit 5 reserved
Bit 6 Set Break
Bit 7 reserved
0x3206 1 ReceiveCount485 Byte counter for Rx-FiFo for RS-485 0x0284
0x3207 1 TransmitCount485 Number of bytes in TX send buffer 0x0285
CAN
Object
Index
Default
CAN
Mapping
Size
(byte)
Local I/O
description
Local I/O
addresses