13 Relay output module XN-322-4DO-RNO
13.3 Wiring topic
XN300 slice modules 02/24 MN050002EN Eaton.com 80
13.3 Wiring topic
A digital output is wired to each of the four X1 to X4 connectors.
13.3.1 Wiring the relay output
The EN 60947-5-1 relay output has the properties specified in EN 61131-2.
Figure 48: Internal logic for relay output
a NO relay contact
b Common contact
The power supply module (the gateway or PLC, for example) must provide a
minimum supply voltage to the relay output module. This voltage depends on
the ambient temperature, as shown in the table below:
((
NOTICE
In order for the relay coil to pick up correctly, the relay output
module needs a minimum supply voltage.
Ambient air temperature
[°C]
Supply voltage
[V]
-25‚…+30
18
+40
18.7
+50 19.4
+60 20.0