15 Digital output module XN-322-8DO-P05
15.1 Pin assignment and status LED signals
XN300 slice modules 02/24 MN050002EN Eaton.com 94
Table 5 Status LED signals
15.1.1 Wiring topic
Four digital outputs can be wired to the X1 connector and another four digital
outputs can be wired to the X2 connector.
15.1.2 Connecting the power supply
The cross-sectional area of the +24 V cables used to supply power must be
sized for the maximum total current drawn by all the outputs.
It is impermissible to apply a voltage, at any output, that exceeds the supply
voltage by more than 0.7 V.
15.1.3 Connecting EN 61131-2 short-circuit proof digital outputs
The outputs are able to drive twice their rated operational current briefly
when driving loads with higher inrush currents.
Module status Green ON System OK
OFF No power
FLASHES (5 Hz) No communications
Status User yellow ON The user can set the LED signals as necessary.
(For example, the visualization interface can be used to
set the module's LED to flash so that it is easier to find
the module inside the control panel.)
OFF
FLASH
(200 ms ON,
1000 ms OFF)
FLASH
(1000 ms ON,
200 ms OFF)
Status of output n
n=1 to 8
yellow ON Output is "ON"
OFF Output is "OFF"
Power status for
digital outputs
Green ON The digital outputs are being powered with 24 VDC
OFF The outputs are not being powered properly (under-
voltage) or the system is not being powered at all. If the
system is not being powered at all, the module status
LED will be OFF.