49 Using The ecobee EMS Thermostat
Temperature Range
You can congure the Thermostat so that only a specic
heat and/or cool set point range is permitted.
Heat Temp Range
Users will not be able to set the Thermostat to a
temperature above this limit.
Cool Temp Range
Users will not be able to set the Thermostat to a
temperature below this limit.
Recovery Options
Recovery options allow the EMS to learn how the heating
and cooling system works, taking into account infrastructure,
weather and historical performance, to eciently recover
from temperature set back or set forward.
Smart Recovery Heat
The EMS will start recovery at the optimum time to ensure
the set point is reached at the programmed time.
Smart Recovery Cool
The EMS will start recovery at the optimum time to ensure
the set point is reached at the programmed time.
Random Start Heat
Programming a time in this section will produce a random
delay when there is call for heat. In applications with
multiple heating systems, this prevents all systems from
activating at the same time, creating a peak power demand.
Random Start Cool
Programming a time in this section will produce a random
delay when there is call for cooling. In applications with
multiple cooling systems, this prevents all systems from
activating at the same time, creating a peak power demand.
Economizer Setting
If a relay output is congured as an Economizer output,
the following options will be made available:
Disable Economizer during Smart Recovery
If enabled, the Economizer relay output will not activate
during Smart Recovery for heat or cool. It will only
activate when the system is in an Occupied period.
If No is selected, the Economizer output will activate during
the recovery from the Unoccupied to Occupied periods.
Perform Pre-occupancy Purge
If enabled, the Pre-occupancy Purge will be activated
a minimum of 1 hour before the transition to an
Occupied period.
Thermostat Name
This section allows you to program a name (i.e. Front
Oce) on the Thermostat. This is useful if you have
multiple systems or zones. You can view the Thermostat
name in the About menu on the Thermostat and also in
your online Web Portal.
Notes
This section allows you to program information you
would like the user or service contractors to know
about the equipment. For example, which roof-top unit
the Thermostat is controlling or where the Equipment
Interface is installed.
Vacation Property
This option puts the ecobee EMS in a mode suitable for
vacation rental properties. With this option enabled, the
Thermostat will normally be programmed to remain in
the unoccupied state (i.e., the property is vacant). The
property manager can then schedule a calendar event
that coincides with rental periods. During this calendar
event, the ecobee EMS will switch to the occupied state
but look and feel like the residential ecobee Smart
Thermostat. The renters will have access to features like
QuickSave, manual adjustments and hold settings (still
within the limits as programmed). Once the calendar
event (i.e., rental period) has elapsed, the Thermostat
will automatically revert back to the unoccupied state.
Using The ecobee EMS Thermostat 50
To view Notes:
From the Home
screen, press More.
Press Settings and
select the About
Menu.