Feature
Description
Range
Default
Setting
Minimum Off time
Sets the Minimum Off Time (MOT) delay before another heating/cooling cycle
can begin. Provides compressor short cycle protection. Wait” is displayed on
screen when active.
5-9 Minutes
5
Heat Setpoint
Max.
Sets the maximum heating setpoint value.
Will not ramp or accept setpoints higher than this maximum
55F to 96F (4C
to 43C)
90F (32C)
Cool Setpoint Min.
Sets the minimum cooling setpoint value
60F to 99F
60F (15C)
(6C-45C)
Heat Blower Off
Sets the system blower delay off time after a heat call ends (fan purge)
0 to 9 seconds
0 (off)
Delay
Cool Blower Off
Sets the system blower delay off time after a cool call ends (fan purge)
0 to9 seconds
0 (off)
Delay
Heat - Cool Delta
Sets the minimum separation between heating and cooling setpoints.
Note:
3 to 15
3F (1C)
Attempts to lower cooling setpoint below the heating setpoint will PUSH the
degrees
heating setpoint down to maintain this separation. The same applies to setting
the heating setpoint above the cooling setpoint, it will PUSH the cooling set-
point up to maintain the setpoint delta separation
Heating Stage 1 on
Sets the delta from setpoint that stage 1 heating starts
1 to 6 degrees
1
Threshold
Heating Stage 1
Sets the delta from setpoint that stage 1 heating stops. Stage 1 turns off at
0 to 5 degrees
0
Off Threshold
setpoint + Delta Stage 1.
Heating Stage 2
Sets the delta from setpoint that stage 2 heating starts
2 to 7 degrees
2
On Threshold
Heating Stage 2
Sets the delay from setpoint that stage 2 heating stops. Stage 2 turns off at
0 to 6 degrees
0
Off Threshold
setpoint + Delta Stage 2.
Aux Heat On
Sets the delta from setpoint that stage 3 heating starts
3 to 8 degrees
3
Threshold
Aux Heat Off
Sets the delta from setpoint that stage 3 heating stops.
0 to 7
0
Threshold
Stage 3 turns off at setpoint + Delta Stage 3
degrees
Cooling Stage 1
Sets the delta from setpoint that stage 1 cooling starts.
1 to 7
1
On Threshold
degrees
Copyright © Ecolink Intelligent Technology
TBZ500_manual_8_5x5_5_inch Combined_RDN1240221.indd 16 24-02-2021 18:55
16

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ecolink Z-Wave TBZ500 and is the answer not in the manual?

Ecolink Z-Wave TBZ500 Specifications

General IconGeneral
BrandEcolink
ModelZ-Wave TBZ500
CategoryThermostat
LanguageEnglish