16
4.4 Connection – Actuator
4.4.1 Single acting actuator – Figure 3301 & 3303
Singe acting type positioner is set to use OUT1 port. OUT1 port should be connected with
the supply pressure port of the actuator when using single acting type of spring return
actuator.
Single acting linear (left) and rotary (right) type actuator
4.4.2 Double acting actuator – Figure 3302 & 3304
Double acting type positioner is set to use OUT1 and OUT2 port. As input signal increases,
the supply pressure will be supplied through OUT1 port.
Double acting linear (left) and rotary (right) type actuator
4.5 Connection – Power
4.5.1 Safety
Conduit entry connection tap is 1/2” NPT with a conduit for 8 mm cable.
Before connecting terminal, ensure that the power is off completely. Do not open the
cover when the power is still alive.
Please use insulated electrical connection ring-type lug to protect against vibration or
any other external impact.
Positioner with PTM options must be supplied 10~28V DC separately. It should not
exceed 30V DC.