Installation and Operating manual
Econ
®
Series 3300 Smart Valve Positioner www.eriks.com www.eriks.com
33
7.2 Warning code
Pv Span – Pv Zero range is below 500.
The angle of feedback lever is too small.
Re-install the positioner.
Ensure the feedback lever does not
touch the lever stopper at 0% and
100%.
After re-installation, perform AUTO1.
Full open/close elapsed time is less
than 1 second.
Actuator size is too small.
Use variable orifice.
Use larger actuator.
Pv is below 100.
The angle of feedback lever is too large.
Re-install the positioner.
Ensure the feedback lever does not
touch the lever stopper at 0% and
100%.
After re-installation, perform AUTO1
Pv is over 4000.
The angle of feedback lever is too large.
Re-install the positioner.
Ensure the feedback lever does not
touch the lever stopper at 0% and
100%.
After re-installation, perform AUTO1