Series 3300 Smart Valve Positioner www.eriks.com www.eriks.com
24
6.3.3.5 P_ (KP_), D_ (Kd_) , I_(KI_) values
P_, D_, and I_ values are principly the same as the P, D, and I values, but these values will
be activated when the error percentage is within 1%.
6.3.4 Hand Calibration Mode (HAND CAL)
The positioner can be manually calibrated by entering into Hand Calibration Mode.
6.3.4.1 Zero-Point (PV_ZERO) and End-Point (PV_END) for Valves
PZ_ZERO adjusts the zero point of the valve, and PV_END adjusts the end point of the
valve.
<ENTER>
<DOWN>
3 times
<ENTER>
<UP><DOWN>
<ESC>
3 times
<ENTER>
<ENTER>
6 seconds
<DOWN>
3 times
<ENTER>
<ENTER>
<UP>/<DOWN>
<ESC>
Zero Adjustment
<ENTER>
<DOWN>
<ENTER>
<UP>/<DOWN>
End Adjustment
<ENTER>
<ESC>