1.2 Programming Manual
How To Begin
Without a careful and well planned approach to programming, the task
of data entry will become unmanageable. The IRC-3 network is very
versatile and capable of performing the same function in many different
ways. Because of the versatility of this program, a high degree of
system understanding and preparation is required to program the
system.
Note: If you have not filled out the program setup worksheets provided
in appendix A of this manual, you are NOT ready to begin the process
of data entry. COMPLETE THE WORKSHEETS FIRST!
The following steps must be completed in the order specified to ensure
a successful program:
1. Complete a system matrix sheet. A matrix sheet indicates the outputs
or functions performed as a result of an input change of state.
2. Complete the cabinet worksheets.
3. Complete the CM1(N) panel worksheet.
4. Complete the CM2(N) panel worksheets.
5. Complete the zone/option card worksheets.
6. Complete the RZB12-6 worksheets.
7. Complete the matrix or SAN annunciator worksheets.
8. Complete the program worksheets in the following order:
1 Actions
2 Time controls
3 Sequences
4 "AND" functions
5 Alarm zone worksheets
6 Supervisory zone worksheets
7 Security zone worksheets
8 Switch worksheets
9. Install IRC-3 Data Entry Program into your PC.
10.Enter data into your PC in the order listed on the data entry menu.
11.Print a listing of the entered data.
12.Compare the data from the listing to the data on your worksheets.
13.Compile the data and download the data to the network panels.
14.Perform a full functional test of the system.