Chapter 3: Programming
36 SIGA-REL Technical Reference Manual
5. Connect to the panel and use the Communication Functions dialog box to
upload the Signature loop.
6. In the Signature Series mapping tool, open the Actual vs. Expected Data
dialog box (F9 key).
7. For the first two SIGA-REL devices, click Commit Expected.
8. For the third SIGA-REL device, click Break Chain, select the first available
address (the release circuit), and click Commit Expected.
Break chain button
9. For the fifth SIGA-REL device, click Break Chain, select the next available
address (the prerelease circuit), and click Commit Expected.
10. Close all Signature Series mapping tool dialog boxes and windows.
11. Perform a Signature Series conversion and download the database to the
panel.
Table 16: SIGA-REL configuration settings
Typical
address [1]
Typical serial
number [1]
Device type
Model
Personality code
0207
5300411525
Monitor
SIGA-REL
N/O Active Nonlatching (Class B)
0208
5300411532
Pull
SIGA-REL
N/O Alarm Latching (Class B)
0209
5300411549
DoorControl
SIGA-REL
Signal Output (Class B)
0210
5300411556
LocalTrouble
SIGA-REL
No personality
0211
5300411563
DoorControl
SIGA-REL
Signal Output (Class B)
0212
5300411570
LocalTrouble
SIGA-REL
No personality
[1] Actual addresses in your system may differ, but they must be consecutive. Serial numbers
must also be consecutive up to the second-to-last digit.