EasyManua.ls Logo

elco THISION S Plus 54 - 1.5 Available flue systems per boiler; 2. Design and sizing information; 2.1 Boiler maximum flue lengths

elco THISION S Plus 54
33 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 6 of 33
1.5 Available flue systems per boiler
Concentric Flue (mm)
Plastic Single Pipe Flue (PPs) (mm)
Thision S Plus
80/125
100/150
Thision S Plus
80
100
110
125
130
34
34
46
46
54
54
Thision L Evo
80/125
100/150
Thision L Evo
80
100
110
125
130
60
60
70
70
80
80
100
100
120
120
140
140
Thision L Eco
80/125
100/150
Thision L Eco
80
100
110
125
130
70
70
100
100
120
120
2. Design and sizing information
2.1 Boiler maximum flue lengths
Thision S Plus
Maximum length in metres for concentric room sealed installations
80/125
100/150
Changes of
direction
0
2
3
4
0
2
3
4
34
25
13.6
7.9
2.2
40
34.2
31.3
28.4
46
12
30
19.4
14.1
8.8
54
11
30
15.4
8.1
0.8
Maximum length in metres for single pipe open or room sealed installations
80mm
100mm
Changes of
direction
0
2
3
4
0
2
3
4
34
30
22
18
14
80
77.1
75.7
74.3
46
12
55
49.9
47.3
44.7
54
11
50
42.9
39.3
35.8

Related product manuals