Here you can set the limit of the minimum adjustable tempera-
ture. When using the GSM module, you will be informed by an
SMS that the room temperature has dropped below this value.
Select within the range from 3°C to 10°C (by 0.5°C).
4
CONTROL TYPE
Press the “ MENU “button twice; select the CONST mode by turning the “
“ button, and
confi rm with the “ “button.
Set the constants depending on the type of building being heated, boiler and heating system.
For select the type of regulation we recommend you consulting with an expert.
Against undesirable usage of strange person we recommend using CONST19 (password).
Language selection (CZ/PL/EN/DE/RU/SK).
Choose the language by turning the“
“ button, and confi rm
with the“ “ button.
MINIMUM CONTROL TEMP.
Set the value by turning the“ “ and confi rm “ “.
MAXIMUM CONTROL TEMP.
(Czech is factory preset)
(factory setting of 5°C)
(factory setting of 39°C)
Here you can set the limit of the maximum adjustable tempera-
ture. When using the GSM module, you will be informed by an
SMS that the room temperature has risen above this value.
Select within the range from 15°C to 39°C (by 0.5°C).
Set the value by turning the“ “ and confi rm “ “.
(PID-regulation is factory preset)
CONSTANTS SETTING
Choose the type of control by turning the “ “ button and
press the “ “ button to confi rm.
HS = Hysteresis
Difference between the desired and current
temperature.
If the hysteresis is 1 °C and the desired temperature is
20 °C, the thermostat switches off at 20 °C, and on at
19 °C (see the graph).
For correct hysteresis function, set the parameters
according to the heating system type; see CONST 5.
Note: If hysteresis is selected, CONST 6 is skipped automatically.
Selection of the control type: