6. SAFETY REGULATIONS
6.1. Only the persons, who have made a close study of the present passport and who have
passed the instructing in the
SAFETY REGULATIONS can be allowed to work with RMT
6.2. RMT correspond to class 1 of STATE STANDARTS 12.2.007.0-75 by its method to
protect a person from electric injuring
6.3. RMT have a clip of protective grounding according to STATE STANDARTS
12.2.007.0-75.
6.4. Before switching on it is necessary to check that RMT grounding exists and is in order.
The grounding resistance should not exceed 0,1 Ohm.
6.5. When using RMT it is necessary to follow STATE STANDARTS 12.3.019-80
instructions, " ” and " Electric device using instructions of safety methods for consumers",
authorized by State Energy Consuming Regulation Department (Госэнергонадзор).
6.6. Perform reparations and all preventive works at the switched - off RMT.
6.7. Connect prime transformers, signal system circuit wires according to the marking when
the power supply is switched – off.
7. PRE-STARTING PROCEDURE
7.1. Unpack the RMT. Make an external examination, when the conformity to the following
requests should be established:
1) RMT should be completed according to section 4 of the present passport;
2) The RMT factory number should correspond the number indicated in the passport;
3) RMT should not have any mechanical damages, when it is forbidden to perform any
working.
7.2. Order of RMT installation
7.2.1. For RMT installation in a board it is necessary to have access to it from the board back
side. The cut dimensions are according article 3.28.
7.2.2. RMT installation in a board is according to the assembly drawing represented in fig.
7.1. Special fixing articles – brackets (C-clamps) are used for RMT fastening, they are included in
the complete delivery set.
Multichannel technological registrar RMT 49D.
Assembly drawing
Fig. 7.1