Note
The blue ejector indicates that the module is correctly seated. If the blue ejector
button does not remain seated, then the module is not fully inserted. Push on the
module handle to complete the seating process.
Reconnect the system
Procedure
1. Engage power by reconnecting all AC power cords.
2. Reconnect the wire clips for the AC cords.
3. Check to see that the service LED on the Management module glows green.
Note
The service LED lights up within 30 seconds after you connect the AC power cords.
4. In the front of the DD9500/DD9800 system, press the power button to turn the power
on the system.
5. Check that the front blue power LED (with the circle with a dot) also turns on.
Figure 3 Power LED and power button
1. Power LED
2. Power button
6. For HA systems that were failed over to the standby node before the component
replacement, optionally fail the ssytem back to the original active node. Run the ha
Field Replacement Guide
8 EMC Data Domain DD9500 and DD9800 Systems Field Replacement Guide