Epsilon Eb and EN Drives Reference Manual
the required KVA rating are high transformer ambient temperatures (>40° C or >104° F) and
drive operation near the maximum speeds.
Transformer output voltage drop may become a limiting factor at motor speeds and loads near
maximum ratings. Typically, higher KVA transformers have lower voltage drop due to lower
impedance.
Drive/Motor Combination Suggested KVA Rating
EN-204/NT-320 3.0
EN-204/MG-205 0.8
EN-204/MG-208 1.5
EN-204/MG-316 2.3
EN-208/NT-320 3.0
EN-208/NT-330 3.9
EN-208/NT-345 4.3
EN-208/NT-355 4.9
EN-208/MG-316 2.3
EN-208/MG-340 3.9
EN-208/MG-455 4.9
EN-214/NT-345 4.3
EN-214/NT-355 4.3
EN-214/MG-455 4.3
EN-214/MG-490 6.0
EN-214/MG-4120 6.5
Eb-202/NT-207 1.0
Eb-202/NT-212 1.2
Eb-203/NT-207 1.0
Eb-203/NT-212 1.7
Eb-203/MG-316 2.3
Eb-205/NT-212 1.7
Eb-205/NT-320 3.0
Eb-205/NT-330 3.0
Eb-205/NT-345 3.0
Eb-205/MG-340 3.0
Eb-205/MG-316 2.3
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Other manuals for Emerson Control Techniques EN Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Control Techniques EN Series and is the answer not in the manual?

Emerson Control Techniques EN Series Specifications

General IconGeneral
BrandEmerson
ModelControl Techniques EN Series
CategoryDC Drives
LanguageEnglish

Related product manuals