Epsilon Eb and EN Drives Reference Manual
 Figure 55: Earth Grounded WYE Distribution Transformer
 Figure 56: Earth Grounded Delta Distribution Transformer
AC Supplies Requiring Transformers
If the distribution transformer is configured as shown in the figures below, an isolation 
transformer is required.
If an isolation transformer is used between the power distribution point and the drives, the 
transformer secondary must be grounded for safety reasons as shown in the figures below.
 Figure 57: Three Phase Delta (with mid-phase GND) Distribution to a Three-Phase 
Delta/WYE Isolation Transformer