EasyManua.ls Logo

Emerson ControlWave EFM 3808 - Process I;O Board; Setting Jumpers on the Process I;O Board; Setting DIP Switches on the Process I;O Board

Emerson ControlWave EFM 3808
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ControlWave Express Instruction Manual (CI-ControlWave Express)
3-2 I/O Configuration and Wiring Revised Mar-2011
3.2 Process I/O Board
ControlWave Express may include an optional Process I/O board.
The Process I/O board mounts to the CPU/System Controller board
using six nylon mounting posts.
To configure the Process I/O board, you need to set some switches and
jumpers. See Figure 3-1 for the location of the switches and jumpers.
3.2.1 Setting Jumpers on the Process I/O Board
The Process I/O board has several jumpers.
JP1: AO output source (1-5V or 4-20mA):
o 1-to-2 Installed = 4-20mA analog output
o 2-to-3 Installed = 1-5V analog output
JP3: AO power source:
o 1-to-2 Installed = system power
o 2-to-3 Installed = external power (+11 to +30 Vdc)
JP4: AI field power configuration:
o 1-to-2 Installed = external 24Vdc power
o 2-to-3 Installed = bulk input supply (system power)
JP5: AI1 input type (1-5V or 4-20mA)
o 1-to-2 Installed = 4-20mA analog input
o 2-to-3 Installed = 1-5V analog input
JP6: AI2 input type (1-5V or 4-20mA)
o 1-to-2 Installed = 4-20mA analog input
o 2-to-3 Installed = 1-5V analog input
JP7: AI3 input type (1-5V or 4-20mA)
o 1-to-2 Installed = 4-20mA analog input
o 2-to-3 Installed = 1-5V analog input
3.2.2 Setting DIP Switches on the Process I/O Board
The Process I/O board includes a single switch bank (SW1) to configure
the frequency for the high speed counters (HSC), the source current for
discrete inputs/counters, and the analog output.
Table 3-2. Process I/O Module Switch SW1
SW1 Function Mode
SW1-1
Frequency for High Speed Counter1 (HSC1)
OFF = 10 kHz (high speed)
ON = 300 Hz (low speed)
SW1-2
Frequency for High Speed Counter2 (HSC2)
OFF = 10 kHz (high speed)
ON = 300 Hz (low speed)
SW1-3
DI/HSC 2mA source current
OFF = disabled
ON = enabled

Table of Contents