1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 13/192
TI620
5. FIRST INSTALLING
5.1 ON BOARD CLOCK (OPTIONAL)
If giving power supply the bottom display shows rtC alternated with a temperature or pressure value, It is
necessary to set the internal clock.
After a power failure, clock back-up battery lasts maximum 3 or 4 days. After this period it is necessary to set
the clock again.
The internal clock is an option and it is not possible to update the instrument; it is necessary to order
the instrument already complete of this features.
5.2 REAL TIME CLOCK SETUP
1. Push MENU key for some seconds until the bottom display shows Hour and the top display shows its
value.
2. Push SET one time: the value is blinking
3. Use the Up and Down keys to adjust it. Push SET one time to confirm; automatically the display shows
next parameter
4. Repeat the operations 2. 3. and 4. for all the RTC parameters:
- Min: minutes (60)
- UdAy: day of the week (Sun = Sunday, Mon =Monday, tuE =Tuesday, UEd = Wednesday, tHu =
Thursday, Fri =Friday, SAt =Saturday)
- dAy: day of the month (31)
- MntH: month (12)
- yEAr: year (00÷99)
6. PARAMETER PROGRAMMING
6.1 PROGRAMMING WITH THE “HOT KEY 64
Download: how to program an instrument with a programmed Hot Key 6.1.1
1. Power off the instrument
2. Insert the hot key already programmed (by software Wizmate or other instrument)
3. Power on the instrument
4. Automatically the parameters are downloaded
During the download the regulation is locked and the top display shows the doL blinking label. At the end
of the download will appear:
“End” if the programming procedure is completely OK, after 30seconds the regulation starts automatically.
“Err” if the programming procedure has found an error and the parameter have not been transferred. In this
case turn off and then on the instrument supply to repeat the operation or remove the hot key, with power
supply off, to restart the regulation.
Upload: How to program a “Hot Key” with the parameters of the instrument 6.1.2
1. Power on the instrument
2. Insert the hot key
3. Enter the function Menu