17
September 2018
SIL Safety Manual
DOC.SILM.EF.EN Rev. 1
Common Cause Factors
Section 10: Common Cause Factors
The product has a single channel conguration, HFT=0.
The β factors can be used when performing PFD
AVG
calculations for redundant
architectures.
The Common Cause factors, relevant when the product is used in redundant conguration,
are: β=β
D
=0,05
NOTE:
The above value is the value for 1oo2 architecture. The values for other architectures
shall be calculated according to IEC 61508 Part 6, Table D.5.
The above value is calculated in the hypothesis of redundancy without diversity.