Operating instruction 
EXD-HP1/2 Controller with ModBus 
communication capability 
 
 
 
Emerson Climate Technologies GmbH   www.climate.emerson.com/en-gb  Date: 17.12.2020 
Am Borsigturm 31 I 13507 Berlin I Germany    EXD-HP12_OI_EN_DE_RU_1220_R06_865921.docx 
Wiring: Upper board (EXD- HP2):  
 
 
Note: 
•  Upper board is only for function of superheat control. 
•  Upper board does not need to be wired if the circuit 2 is disabled. 
 
Preparation for Start- up: 
•  Vacuum the entire refrigeration circuit. 
•    Warning:  Electrical Control Valves EXM/EXL or  EXN are delivered 
partially open position. Do not charge system with refrigerant before closure 
of valve. 
•  Apply supply voltage 24V to EXD-HP1/2 while the digital input (DI1/DI2) is 
OFF(open). The valve will be driven to close position. 
•  After closure of valve, start to charge the system with refrigerant. 
Setup of parameters: 
(need to be checked/modified before start-up) 
•  Make sure that digital input (DI1/DI2) is off (open). Turn the power supply ON. 
•  Four main parameters Password (H5), type of function (1uE), refrigerant type 
(1u0/2u0) and pressure sensor type (1uP/2uP) can be set only when digital input 
DI1/DI2 is off (open) while the power supply is ON (24V). This feature is for added 
safety to prevent accidental damage of compressors and other system components. 
•  Once the main parameters have been selected/saved the EXD-HP1/2 is ready for 
startup. All other parameters can be modified at any time during operation or 
standby if it is necessary. 
Display/keypad unit (LEDs and button functions):  
 
 
 
   
 
 
 
 
 
Procedure for parameter modification: 
The parameters can be accessed via the 4-button keypad. The configuration 
parameters are protected by a numerical password. The default password is “12”. To 
select the parameter configuration: 
•  Press the   button for more than 5 seconds, A flashing “0” is displayed 
•  Press   until “12” is displayed; (password) 
•  Press   to confirm password 
•  Press  or   to show the code of the parameter that has to be changed 
•  Press   to display the selected parameter value 
•  Press  or   to increase or decrease the value 
•  Press   to temporarily confirm the new value and display its code 
•  Repeat the procedure from the beginning "press  or   to show..." 
To exit and save the new settings: 
•  Press    to confirm the new values and exit the parameters modification 
procedure. 
To exit without modifying/saving any parameters: 
•  Do not press any button for at least 60 seconds (TIME OUT). 
Reset all parameters to factory setting: 
•  Make sure that digital input (DI1/DI2) is Off (open). 
•  Press   and   together for more than 5 seconds. 
•  A flashing “0” is displayed. 
•  Press  or   until the password is displayed (Factory setting = 12).  
•  If password was changed, select the new password. 
•  Press   to confirm password 
•  Factory setting are applied 
Note: In standard mode the actual superheat is shown at the display. In case of liquid 
injection and economizer function this change to discharge temperature. 
•  To display other data of circuit 1 of EXD-HP1/2 or 2 of EXD-HP2:  
– Press   and   together for 3 seconds to show data of circuit 1 
– Press   and   together for 3 seconds to show data of circuit 2 
•  To display data of each circuit: Press the    button for 1 second until index 
number according to the below table appears. Release the   button and the next 
variable data will appear. By repeating above procedure, variable data can be 
displayed in a sequence as Measured superheat (K) → Measured suction pressure 
(bar)  →  Valve  position  (%)  →  Measured  suction  gas  temperature  (°C)  → 
Calculated saturated temperature (°C) → Measured discharge temperature (°C) (if 
economizer function is selected) →REPEATING…. 
Note 1: Discharge temp. is available only if economizer function is selected. 
Note 2: After 30 minutes, display reverts to index 0.
Blinking: valve is closing 
ON: valve is fully close 
Blinking: valve is opening 
ON: valve is fully open 
Parameters setting/saving 
confirming 
Next parameter/ 
value (higher) 
Next parameter/ 
value (lower) 
ON: Data display 
Circuit 1 
ON: Data display 
Circuit 2