Operating instruction
EXD-HP1/2 Controller with ModBus
communication capability
Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 17.12.2020
Am Borsigturm 31 I 13507 Berlin I Germany EXD-HP12_OI_EN_DE_RU_1220_R06_865921.docx
Manual alarm reset/clearing functional alarms (except hardware errors):
Press and together for 5 seconds. When the clearing is done, “CL”
message appears for 2 seconds.
Manual mode operation
Press and together for 5 seconds to access to manual mode operation.
List of parameters in scrolling sequence by pressing button
Code
Parameter description and choices
Min Max
Manual mode operation; circuit 1
Manual mode operation; circuit 2
Note: During manual operation, functional alarms such as low superheat are
disabled. It is recommended to monitor the system operation when the controller
is operated manually. Manual operation is intended for service or temporary
operation of valve at a specific condition. After achieving the required operation,
set the parameter 1Ho and 2Ho at 0 so the controller automatically operates the
valve(s) according to its setpoint(s).
List of parameters in scrolling sequence by pressing
button:
Code Parameter description and choices Min Max
Circuit 2 of EXD-HP2 enabled
0 = Enabled; 1 = Disabled
0 = °C, K, bar; 1 = F, psig
This Parameter effects only the display. Internally the units are allways SI-
0 = No display 1 = Circuit 1 2 = Circuit 2 (only EXD-HP2)
Parameters Circuit 1
0 = Superheat control
1 = Economizer control (Only for R410A/R407C/R32)
0 = Standard control coil heat exchanger
1 = Slow control coil heat exchanger
2 = fixed PID
3 = fast control plate heat exchanger (not for 1uE = 1)
4 = Standard plate heat exchanger (not for 1uE = 1)
0 = R22 1 = R134a 2 = R410A 3 = R32 4 = R407C
5 = R290* 6 = R448A 7 = R449A 8 = R452A 9 = R454A*
10 = R454B* 11 = R454C* 12 = R513A 13 = R452B* 14 = R1234ze*
15 = R1234yf *
*) EXN not permitted
*) Warning -Flammable refrigerants: EXD-HP1/2
has a potential
ignition source and does not comply with ATEX requirements. Installation
only in non-explosive environment. For flammable refrigerants only u
se
valves and accessories approved for it!
Installed pressure sensor type
0 = PT5N-07… 1 = PT5N-18…
2 = PT5N-30… 3 = PT5N-10P-FLR
Start opening duration (second)
Low superheat alarm function
0 = disable (for flooded evaporator) 1 = enable auto reset
2 = enable manual reset
If 1uL = 1 or 2 (enabled auto or manual reset)
3
30
6
MOP set-point (°C) saturation temperature
Factory setting according to selected refrigerant
(1u0). The default value can be changed
Code Parameter description and choices Min Max
Low pressure alarm mode circuit 1
0 = disabled 1 = enabled auto reset
2 = enabled manual reset
Low pressure alarm cut-out circuit 1
Low pressure alarm delay circuit 1
Low pressure alarm cut-in circuit 1
Freeze protection alarm function
0 = disabled, 1 = enabled auto-reset,
2 = enabled manual reset
Freeze alarm cut-out circuit 1
Freeze protection alarm delay, sec.
Superheat control circuit 1 fixed PID (Kp factor)
Display 1/10K
Superheat control circuit 1 fixed PID (Ti factor)
Superheat control circuit 1 fixed PID (Td factor)
Display 1/10K
Hotgas temperature sensor source
0 = ECP-P30
1 = Via Modbus input
Economizer control circuit 1 fixed PID
(Kp factor) Display 1/10K
Economizer control circuit 1 fixed PID
(Ti factor)
Economizer control circuit 1 fixed PID
(Td factor) Display 1/10K
1uH
High superheat alarm mode circuit 1
0 = diabled 1 = enabled auto-reset
0 1 0
High superheat alarm setpoint circuit 1
High superheat alarm delay circuit 1
1E2
Positive correction of measured Hotgas
temperature.
0 10 0
Parameters Circuit 2 (only EXD
-HP2)
Code Parameter description and choices Min Max
0 = Standard control coil heat exchanger
1 = Slow
control coil heat exchanger
3 = fast control plate heat exchanger
4 = Standard plate heat exchanger
0 = R22 1 = R134a 2 = R410A 3 = R32 4 = R407C
5 = R290* 6 = R448A 7 = R449A 8 = R452A 9 = R454A*
11 = R454C* 12 = R513A 13 = R452B* 14 = R1234ze*
Warning -Flammable refrigerants: EXD-HP1/2 has a potential
ignition source and does not comply with ATEX requirements. Installa
tion
-explosive environment. For flammable refrigerants only use
valves and accessories approved for it!
Installed pressure sensor type
(When DI2 is off)
0 = PT5N-07… 1 = PT5N-18…
2 = PT5N-30… 3 = PT5N-10P-FLR
Start opening duration (second)
Low superheat alarm function
0 = disable (for flooded evaporator) 1 = enable auto reset
2 = enable manual reset
Superheat set-point (K)
If 2uL = 1 or 2
(enabled auto or manual reset)
3
30
6
MOP set-point (°C) saturation temperature
Factory setting according to selected refrigerant
(2u0). The default value can be changed
2P9
Low pressure alarm mode circuit 2
0 = disabled 1 = enabled auto reset
2 = enabled manual reset
Low pressure alarm cut-out (bar) circuit 2
Low pressure alarm delay (sec) circuit 2
Low pressure alarm cut-in (bar) circuit 2
Freeze protection alarm function
0 = disable, 1 = enable auto-reset,
2 = enable manual reset