Operating instructions
EXD-TEVI Economizer Controller with
ModBus Communication Capability
Emerson Climate Technologies GmbH www.emersonclimate.eu 2/3
Holzhauser Straße 180 I 13509 Berlin I Germany Date: 19.08.2014 EXD-TEVI_OI_EN_R02_865908.docx
Preparation for Start-up:
Vacuum the entire refrigeration circuit.
EMERSON’s Electrical Control Valves EXM/EXL are delivered in partially
open position. Do not charge system with refrigerant before closure of valve.
Procedure for Valve Closure:
Apply supply voltage 24V to EXD-TEVI while the digital inputs (DI1 and DI2)
are Off (open). The valve(s) will be driven to close position.
After closure of valve, start to charge the system with refrigerant.
Setup of parameters
(need to be checked/modified before start-up):
Make sure that digital inputs (DI1 and DI2) are off (open).
Turn the power supply ON.
Once the main parameters have been selected/saved the EXD-TEVI is ready for
startup. All other parameters can be modified at any time during operation or
standby if it is necessary.
Procedure for parameter modification:
The parameters can be accessed via the 4-button keypad. The configuration
parameters are protected by a numerical password. The default password is “12”.
To select the parameter configuration:
Press the button for more than 5 seconds
A flashing “0” is displayed
Press until “12” is displayed; (password)
Press to confirm password
The 1
st
parameter H5 is displayed
Press or to show the code of the parameter that has to be changed
Press to display the selected parameter value
Press or to increase or decrease the value
Press to temporarily confirm the new value and display its code
Repeat the procedure from the beginning "press or to show..."
To exit and save the new settings:
Press to confirm the new values and exit the parameters modification
procedure.
To exit without modifying/saving any parameters. do not press any button for at
least 60 seconds (TIME OUT).
Reset all parameters to factory setting:
Make sure that digital inputs (DI1/DI2) are Off (open).
Press and together for more than 5 seconds.
A flashing “0” is displayed.
Press or until the password is displayed (Factory setting = 12).
If password was changed, select the new password.
Press to confirm password
Factory setting are applied
Display System Parameters:
In standard mode the EVI superheat is shown at the display. In case of wet vapor
injection and economizer function this changes to discharge temperature.
To display other data of EXD-TEVI:
Press for 3 seconds to show data
To display data: Press the button for 1 second until index number according
to the below table appears. Release the button and the next variable data will
appear. By repeating above procedure, variable data can be displayed in a sequence
as in following table.
Index No. Variable data Units
Source
0 Default displayed value
K measured
1 EVI Pressure bar measured
2 Total combination
Valves opening
%
3 EVI suction gas temp °C measured
4 EVI saturation temp. °C calculated
5 Discharge temp. 1 °C measured
6 Discharge temp. 2 °C measured
Note: After 3 minutes, display reverts to index 0.
Manual alarm reset/clearing functional alarms (except
hardware errors):
Press and together for 5 seconds.
When the clearing is done, “CL” message appears for 2 seconds.
List of parameters in scrolling sequence by pressing
button:
Code
Parameter description and choices
Min Max
Factory
setting
H5 Password 1 1999
12
Adr ModBus address 1 127 1
br Modbus baud rate 0 1 1
PAr Modbus parity 0 1 0
tAn Single / Tandem Operation 1 2 2
1 = single compressor, 2 = tandem compressor
1u4 Superheat control mode 0 2 1
0 = Standard; 1 = Slow;
2 = Fix PID (For trouble shooting/no warranty if system to be
operated with fix PID)
1uu Start valve opening (%) 5 100 15
1u9 Start opening duration (second) 1 30 5
1u5 Superheat set-point (1/10 K) 0.5 30.0 7.0
1PE Economizer control fixed PID (Kp
factor; 1/10)
0.1 10.0 2.0
For trouble shooting/no warranty if system to be operated with PID
1IE Economizer control circuit1 (Ti factor)
1 350 100
For trouble shooting/no warranty if system to be operated with PID
1dE Economizer control circuit1 (Td factor
;
1/10)
0.1 30.0 1.0
For trouble shooting/no warranty if system to be operated with PID
1uC Units conversion 0 1 0
0 = °C, K, bar; 1 = F, psig
1dt Discharge temperature limit (1/100 °C)
100.0 140.0 135.0
1Lo Load shedding valve offset 10 20 18
(Valve opening change by adding/removing compressors.
10 is no offset, 20 is 50% of current valve opening as offset)
dAd Discharge temp. alarm delay (sec) 10 60 60
EC0
Number of installed expansion valves
1 2 1
t2E Threshold start second valve (%) 0 50 30
Control (valve) start-up behavior (Parameter 1uu and 1u9)
1uu:
Min.: 0% (<1 sec.)
Default: 15% (< 1.5 sec.)
Max.: 100% (< 6 sec.)