EC3-P33 Superheat Controller and  
ECD-002 Keypad / Display Unit 
Installation in non explosive environment 
 
 
 
Emerson Climate Technologies GmbH   www.emersonclimate.eu 
Am Borsigturm 31 I 13507 Berlin I Germany  Date: 04.05.2017  EC3-P33_OI_ML_R01_865919.docx 
General information: 
EC3-P33  is the superheat controller for systems with flammable refrigerants 
(A2L/A3) and able to drive EMERSON Valves EX4-7-…FLR via M12 Connector 
ECV05A. 
Note: This document contains short form instructions for experienced users. 
 
Warning: 
•  EC3-P33 has a potential ignition source and does not comply with ATEX 
requirements. Installation only in non-explosive environment. 
•  EX4-7…FLR are currently released for R290 in term of compatibility. The 
other listed refrigerants are subject to qualification at later stage. No 
warranty or product liability if EX4-7…FLR to be used with other 
refrigerants stored in software of EC3-P33. 
 Safety instructions: 
•  Read operating instructions thoroughly. Failure to comply can result in device 
failure, system damage or personal injury. 
•  According to EN 13313 it is intended for use by persons having the 
appropriate knowledge and skill. 
•  Ensure that the system is correctly labeled with applied refrigerant type and 
a warning for explosion risk. 
•  Do not exceed the specified maximum ratings for temperature (max.+60°C), 
voltage and current. 
•  Before installation or service disconnect all voltages from system and device. 
•  Do not operate system before all cable connections are completed. 
•  Entire electrical connections have to comply with local regulations. 
Note: The EC3-P33 series contains a VRLA battery = valve regulated rechargeable 
lead-acid battery. The battery must NOT be disposed of with other commercial waste. 
Instead, it is the user’s responsibility to pass it to a designated collection point for the 
safe recycling of batteries (harmonized directive 2012/19/EU). For further 
information contact your local environmental recycling center. 
 
Mounting position: 
The EC3-P33 is designed to be mounted onto a standard DIN rail. Mounting position: 
on vertical walls, with stepper motor connector on top side only. 
 
Mounting of ECD-002: 
•  ECD-002 can be installed at any time also during operation. 
•  ECD-002 can be mounted in panels with 
71x29 mm cutout. 
•  Push controller into panel cut-out.(1) 
•  Make sure that mounting lugs are flush with 
outside of controller housing 
•  Insert Allen key into front panel holes and turn 
clockwise. Mounting lugs will turn and gradually 
move towards panel (2) 
• 
Turn Allen key until mounting lug barely touches 
panel. Then move other mounting lug to the same 
position (3) 
•  Tighten both sides very carefully until keypad is 
secured. Do not over tighten as mounting lugs 
 
 Electrical Installation: 
•  Refer to the electrical wiring diagram for electrical connections. 
•  Do not apply voltage to the controller before completion of wiring. 
•  Ground the metal housing with a 6.3 mm spade connector. 
•  Keep controller and sensor wiring well separated from mains wiring. 
Minimum recommended distance 30 mm!
  
•  Ensure that cables are not mounted near sharp edges. 
•  Use a class II category transformer for 24 VAC power supply. Do not ground the 
24 VAC lines. We recommend using individual transformers for EC3 controller(s) 
and for 3
rd
 party controllers to avoid possible interference or grounding problems 
in the power supply. 
•  Connecting any EC3 inputs to mains voltage will permanently damage the EC3. 
•  The use of the relay is essential to protect the system in case of power failure if the 
communications interface or the ECD-002 are not utilized. 
•  If the output relay is not utilized, the user must ensure appropriate safety pre-
cautions are in place to protect the system against damage caused by a power 
failure. 
•  In order to provide system protection in the event of power loss, it is recommended 
to change the battery annually. 
 
Digital input status is dependent to operation of compressor/thermostat 
Demand (compressor must be ON) 
 
Wiring:
   
 
 
 
 
v 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
2:  White wire   4:  Black wire  3:  Blue wire  1: Brown wire 
G:  Remote control panel, system controller 
H:  Alarm relay, dry contact. Relay coil is not energized at alarm or power off. 
I:  Digital input (0V/open = Stop; 24 V/closed = Start) 
J:  Transformer Class II, 24 VAC secondary / 25 VA 
K:  Third party controller (can use the analog output signal from EC3) 
 
Preparation for Start-up: 
•  Vacuum the entire refrigeration system 
•  Note: EX4-7-…FLR are delivered at half open position. Do not charge system 
before closure of valve. 
•  Apply supply voltage 24 V to EC3 while the digital input is 0 V (open). The valve 
will be driven to close position.  
•  After closure of valve, start to charge the system with refrigerant. 
•  Start the system and check the superheat and operating conditions.