EasyManuals Logo

Emerson EXD-U01 User Manual

Emerson EXD-U01
7 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Operating Instructions
Universal Driver Module EXD-U01
for Electrical Control Valves
EX4 … EX8 / CX4 … CX7
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 07.12.2015 EXD-U01_OI_ML_R02_865910.docx
General information:
EXD-U01 Universal Driver Module is for driving Emerson stepper motor driven
electrical control valves series EX4…EX8 / CX4…CX7.
Safety instructions:
Read operating instructions thoroughly. Failure to comply can result in
device failure, system damage or personal injury
According to EN 13313 it is intended for use by persons having the
appropriate knowledge and skill.
Before wiring disconnect all voltages from system and device.
Do not operate system before all cable connections are completed.
Do not apply 110/220/230V to any terminal of driver module
Entire electrical connections have to comply with local regulations.
Installation and wiring
Install electrical control valve in system according to operating instructions of
valve.
Install Driver Module and other external electronic devices as shown in wiring
diagram (see Fig. 2).
Keep separate the wires for power supply, stepper motor of valve and signal.
Recommended wire size Ø 0.5 … 2.5 mm
2
.
Setting (Fig.1):
Disconnect voltage
Set dip switches as per table below
Dip Switch Number
Valve / Analog Input
1
2
3
4
EX4-6
OFF
ON
ON
OFF
CX4-6
OFF
ON
ON
OFF
EX7
ON
OFF
OFF
ON
CX7
ON
OFF
OFF
ON
EX8
ON
ON
OFF
ON
4-20 mA
-
-
-
-
0-10V
-
-
-
-
Startup procedure:
The valve must be closed before system charging in case of expansion valve or
hot gas bypass function. The valves are delivered at half open position.
Valve closure:
Remove 24 V from digital input.
Apply supply voltage to driver for the minimum time in below table: (valve
motor makes a characteristic sound until it reaches the closed position)
Valve
Minimum closing time [s]
EX4-6/CX4-6
2…30
EX7/CX7/EX8
6…30
After closure of valve evacuate the entire system.
Then charge the system with refrigerant.
Turn on digital input (24V)
Start the system and check operating conditions.
Valve Synchronization:
After power up EXD-U01 synchronizes the stepper motor driven valve with the
reference point in the fully closed position.
Technical data, power supply:
Main supply voltage: 24 VAC ±10%, 50-60 Hz (use 1.0 A external fuse).
Note: 24 VDC supply voltage can be used but it results to lower MOPD and it
needs to be verified by system manufacture.
Use a safety class II transformer.
Minimum power required 20 VA.
Emergency supply voltage Ub (from ECP-024): +18 VDC.
Inputs:
1 analog input 4…20 mA, burden 364 , or
1 analog input 010 V, impedance 27 k.
1 digital input: 24 VAC/DC (+10%, -15%), 50-60 Hz.
Outputs:
4 current outputs for stepper motor of EX4…EX8/ CX4…CX7.
Uninterruptible power supply ECP-024
Power supply voltage: 24 VAC ± 10%
Power outputs: two, each +18 VDC
Wiring Diagram (see Fig. 2)
(1) = Supply voltage
(2) = Transformer
(3) = Fuse 1.0 A
(5) = Plug cable assembly EXV-Mxx for connection to EX4…EX8 / CX4…CX7
Cable color code
WH = White BK = Black
BL = Blue BN = Brown
(6) = Controller supplies 4…20 mA or 0…10 V
(7) = Digital input signal (0 V = OFF; 24 V = ON)
(8) = Analog input signal (4…20 mA or 0…10 V)
(9) = Optional Uninterruptible Power Supply insures the closure of valve during
power failures in systems, where a valve with positive shut-off function is
needed
Marking: ,
!
Библиотека СОК

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson EXD-U01 and is the answer not in the manual?

Emerson EXD-U01 Specifications

General IconGeneral
BrandEmerson
ModelEXD-U01
CategoryControl Unit
LanguageEnglish

Related product manuals