Fisher
2502 Controllers
Contents
Introduction 2.................................
Scope of Manual 2.............................
Description 2.................................
Specifications 2...............................
Educational Services 2.........................
Installation 4..................................
249 Sensors 5................................
Uncrating 5..................................
Controller Orientation 6........................
Controller‐Sensor Action 6......................
Mounting Caged Sensors 7.....................
Mounting Cageless Sensors 9...................
Side‐Mounted Sensor 9.....................
Top‐Mounted Sensor 10....................
Supply Pressure 11............................
Prestartup Checks 12...........................
Adjustments 13...............................
Level Set Adjustment 13....................
Proportional Band Adjustment 13............
Reset Adjustment 14.......................
Differential Relief Adjustment 15.............
Calibration 15..................................
Precalibration Requirements 15.................
Wet Calibration 15.........................
Dry Calibration 15.........................
Controller and Torque Tube Arm
Disassembly 16.........................
Determining Suspended Weight
for Calibration 16........................
Calibration Procedure 17.......................
Startup 18.....................................
Principle of Operation 19........................
2502 Controller 21............................
2502F Controller with Reset
Relief Valve 21..............................
Maintenance 22................................
Troubleshooting 23............................
Removing Controller from Sensor 24.............
2502 CONTROLLER
249B SENSOR
W8334
Figure 1. Fisher 2502 Controller Mounted on 249B
Sensor
Changing Mounting Method 25.................
Installing Controller on Sensor 26................
Changing Proportional, Reset, or
Differential Relief Valve 27..................
Testing Relay Dead Band 27.....................
Changing Relay 27.............................
Replacing Bellows 27..........................
Reversing Action 28...........................
Parts Ordering 29...............................
Parts Kits 29...................................
Parts List 29...................................
Instruction Manual
D200126X012
2502 Controllers
June 2017

Questions and Answers

  • D
    dianabaileyAug 2, 2025
    What to do if Emerson Fisher 2502 Controller cannot attain full output range?
    • D
      Danielle WhiteAug 3, 2025
      If the Emerson Controller cannot attain its full output range, first reset the regulator pressure. If the issue continues, consider replacing or rebuilding the regulator, ensuring the regulator's input supply pressure remains within specified limits across all operating levels. Also, inspect the flapper assembly, replacing or tightening it and ensuring it is centered on the nozzle. Check if the process variable has changed and return it to the original specification or recalibrate. If necessary, replace the displacer with the correct size and recalibrate. Depress the plunger to clear any fixed restriction if there is a relay malfunction, and replace the relay. Finally, address any leaks in the controller loop by replacing or repairing the affected parts.
  • F
    Frank ThompsonAug 13, 2025
    How to stop Emerson Controller process from wandering?
    • L
      Lisa GarnerAug 13, 2025
      If the Emerson Controller's process wanders or cycles around the setpoint, you should first tune the control loop. Ensure the correct supply pressure is applied, ideally using one regulator per instrument, if the supply pressure is varying or incorrect. Check that the sensor is correctly plumbed, the displacer and rod hang freely, and the linkage is tight; replace the displacer if it's leaking. Depress the plunger to clean out the fixed restriction if there is a relay malfunction. Replace or repair the relay.
  • C
    Claudia HensonAug 21, 2025
    What to do if Emerson Fisher 2502 remains at full output pressure?
    • W
      williamsbrandonAug 21, 2025
      If the Emerson Controller remains at full or zero output pressure, replace the pressure gauges if there is a supply or output pressure gauge malfunction. Replace or tighten the flapper assembly and/or center the flapper on the nozzle if there is a flapper adjustment.

Summary

Introduction

Specifications

Details general specifications of 2502 controllers.

Performance

Lists key performance metrics like hysteresis and repeatability.

Installation

249 Sensors

Describes different types of 249 sensors and their mounting.

Controller-Sensor Action

Explains direct and reverse action based on mounting.

Mounting Caged Sensor

Details plumb installation and cage connections for caged sensors.

Mounting Cageless Sensor

Instructions for installing cageless sensors with stillwells or without.

Side-Mounted Sensor

Describes side-mounting procedures for sensors and displacer attachment.

Top-Mounted Sensor

Details installing top-mounted cageless sensors and displacer rod connection.

Supply Pressure

Prestartup Checks

Adjustments

Level Set Adjustment

How to adjust the level set point using the RAISE LEVEL dial.

Proportional Band Adjustment

Procedure to adjust proportional band via a knob.

Reset Adjustment

How to adjust the reset rate in minutes per repeat.

Calibration

Calibration Procedure

Step-by-step guide for calibrating the controller.

Startup

Principle of Operation

Maintenance

Troubleshooting

Parts Ordering

Emerson Fisher 2502 Specifications