11
Table 6. Hazardous Area Classifications for Fisher 582i Converter
(1)
—ATEX
Certificate Certification Obtained Entity Rating Temperature Code Enclosure Rating
ATEX
II 1 G & D
Intrinsically Safe
Gas
Ex ia IIC T4/T5/T6
Ui = 30 VDC
Ii = 150 mA
Pi = 1.25 W
Ci = 0 nF
Li = 0 mH
T4 (Tamb 71°C)
T5 (Tamb 62°C)
T6 (Tamb 47°C)
IP64
Dust
Ex iaD 20 IP64 T109°C (Tamb 71°C) / T100°C
(Tamb v 62°C) / T85°C (Tamb 47°C)
- - -
II 2 G & D
Flameproof
Gas
Ex d IIC T6
- - - T6 (Tamb 71°C)
IP64
Dust
Ex tD A21 IP64 T74°C (Tamb 71°C)
- - -
II 3 G & D
Type n
Gas
Ex nA IIC T6
- - -
T6 (Tamb 71°C)
IP64
Dust
Ex tD A21 IP64 T74°C (Tamb 71°C)
- - -
1.These hazardous area classification also apply to 3582i positioners.