Instruction Manual
D104161X012
D3 Valve with Gen 2 easy-Drive Actuator
February 2021
33
Table 5. Diagnostic Fault Flags
Hex Value Bit Mask Description Value Bit Definition
0x8000 1000 0000 0000 0000
Fault in N.V. Memory – system has restored
default settings
32768 15
A memory fault has occurred and the actuator
has been restored to factory defaults. Contact
your Emerson sales office
.
0x8000 1000 0000 0000 0000
Fault in N.V. Memory – system has restored
default settings
32768 15
A memory fault has occurred and the actuator
has been restored to factory defaults. Contact
your Emerson sales office.
0x4000 0100 0000 0000 0000 Motor Assembly Stall 16384 14
The actuator is unable to move to the
commanded position and has stopped.  Follow
troubleshooting guide in Help section to remedy.
0x2000 0010 0000 0000 0000 Discrete Input override mode active 8192 13
The digital input has detected a closed contact
and the actuator has moved to its safe position.
Check switch input device status.
0x1000 0001 0000 0000 0000 System or Watchdog fault 4096 12
The actuator has experienced a fatal error and
shut down. Contact your Emerson sales office.
0x0800 0000 1000 0000 0000
Analog Input calibration value not in expected
range
2048 11
The analog values entered do not match the
analog signal level. Check analog signal value and
value entered.
0x0400 0000 0100 0000 0000
Valve travel distance calibration not in legal
range
1024 10
The valve travel distance is outside the
acceptable range. Confirm valve type and that no
obstructions are present.
0x0200 0000 0010 0000 0000 Analog Input span calibration not in legal range 512 9
The analog values for open and close are less
than 4mA and previous values have been
maintained. Calibrate analog input with
differential >4mA.
0x0100 0000 0001 0000 0000 256 8
0x0080 0000 0000 1000 0000 Valve was shutdown while moving 128 7
Actuator was powered down during a move and
actual position may vary from commanded.
Recalibrate the valve span.
0x0040 0000 0000 0100 0000 Valve span calibrated (informational) 64 6 Span has been calibrated and actuator is ready.
0x0020 0000 0000 0010 0000 Valve position controller active (informational) 32 5 Actuator is active and ready.
0x0010 0000 0000 0001 0000 Loss of signal active 16 4
Control signal not present. Signal is <3mA,
timeout period exceeded (40051 or 40052).
0x0008 0000 0000 0000 1000 8 3
0x0004 0000 0000 0000 0100
Modbus command has been sent (starts a
calibrated system)
4 2 The actuator is successfully moving the valve.
0x0002 0000 0000 0000 0010
Analog input initialized (system has seen input
>3mA/1V)
2 1 4-20mA analog input has a valid signal present
0x0001 0000 0000 0000 0001
Start delay active (within 15 second calibration
window)
1 0
Span calibration using physical inputs allowed
during startup