Appendix A - Modbus
A.1 Register Summary
Table 4. Gen 2 easy-Drive Actuator Modbus Map
Type
(1)
Name MB Register Default R/W Values Notes
uint16
Modbus position command
(100=10.0%)
40001 0 R/W 0-1000
Modbus command value with one implied decimal
place (1000=100.0%). R/W at all times but only used in
Modbus control mode. In on/off mode 0-499 will result
in a move to 0% and 500-1000 will result in a move to
100%.
uint16 Digital output 40002 0 R/W 0,1
0=no voltage supplied to terminals,
1=voltage supplied to terminals (Only used when
output setup is set for Remote controlled)
uint16 Reset error codes 40003 0 R/W 0,1
Value of 1 will clear faults. Will automatically set back
to 0.
uint16 RESERVED 40004
uint16 RESERVED 40005
uint16 RESERVED 40006
uint16 RESERVED 40007
uint16 RESERVED 40008
uint16 RESERVED 40009
uint16 Actual position (100=10.0%) 40010 0 R 0-1000
Present position of the actuator relative to span with 1
implied decimal place (1000=100.0%). Valid for all
control modes.
uint16
Commanded position
(100=10.0%)
40011 0 R 0-1000
Present position command of the actuator relative to
span (1000=100.0%). Valid for all control modes.
uint16 Diagnostic Flags 40012 0 R 0-65535 Bit flags - see chart
uint16 Digital status 40013 0 R 0 - 1
0=no connection between terminals, 1=connection
between terminals (Status of digital input or output)
uint32 Total Running Time (min) 40014, 40015 0 R 4294967296
Total number of minutes the actuator has been
powered on since time has been reset
uint32 Total Open Time (min) 40016, 40017 0 R 4294967296
Total number of minutes the actuator has been at
100% of travel since time has been reset
uint32 Total Closed Time (min) 40018, 40019 0 R 4294967296
Total number of minutes the actuator has been at 0%
of travel since time has been reset
uint32 Number of Closed (Cycle count) 40020, 40021 0 R 4294967296
Total number of close cycles the actuator has
performed since reset. One open/close cycle counts as
1.
uint32 Number of Power Cycles 40022, 40023 0 R 4294967296
Total number of times the actuator has been powered
on.
uint32 Number of Movements 40024, 40025 0 R 4294967296
Total number of movements the actuator has
performed. Move must be at least 5% of rated travel for
cycle to increment.
uint16 Analog input control value 40026 0 R 0-2400
Value of the analog signal in mA with 2 implied
decimals. In analog control mode, this is the command
value and is subject to the analog settings in registers
40046 to 40059. Always active but a slower refresh
rate when unit is not in analog control mode.
uint16 Incoming voltage 40027 0 R 0-350
Diagnostic register - value of incoming voltage with 1
implied decimal.
uint16 Latch Open State 40028 0 R 0 - 1 Normally open latch state
-Continued-