Instruction Manual
D104161X012
D3 Valve with Gen 2 easy-Drive Actuator
February 2021
30
Table 4. Gen 2 easy-Drive Actuator Modbus Map (cont.)
Type Name MB Register Default R/W Values Notes
uint16 Latch Close State 40029 0 R 0 - 1 Normally closed latch state
uint16 RESERVED 40030
uint16 RESERVED 40031
uint16 RESERVED 40032
uint16 RESERVED 40033
uint16 RESERVED 40034
uint16 RESERVED 40035
uint16 RESERVED 40036
uint16 RESERVED 40037
uint16 RESERVED 40038
uint16 RESERVED 40039
uint16 Test Register - 16 bit 40040 45964 R 45964
Fixed register to test correct reading of 16 bit registers
- Hex=B38C, Binary=1011001110001100
uint32 Test Register - 32 bit 40041, 40042 3,012,341,331 R 3,012,341,331
Fixed register to test correct reading of 32 bit registers
- Hex=B38C AE53, Binary=1011001110001100
1010111001010011
uint16 Span calibration 40043 0 R/W 0,1
Value of 1 will initiate span calibration. Will
automatically set back to 0.
uint16 RESERVED 40044
uint16 RESERVED 40045
uint16 RESERVED 40046
uint16 RESERVED 40047
uint16 RESERVED 40048
uint16 RESERVED 40049
uint16
Loss of signal position
(100=10.0%)
40050 0 R/W 0-1001
Position to which valve plug will be driven upon loss of
signal. Loss of signal is based upon the active control
mode. 0-1000=0-100.0% with 1 implied decimal point.
In on/off mode 0-499 will result in movement to 0%
while 500-1000 will result in movement to 100%. A
value of 1001 in any control mode is the setting for
"lock-in-last".
uint16 Modbus timeout (s) 40051 60 R/W 0-65535
Time without a valid Modbus message is seen (to any
address) before "loss of signal" motion is engaged
when in Modbus control mode. Only active in Modbus
control mode. 0=disabled
uint16 Dual contact timeout (s) 40052 60 R/W 0-3600
Time without a digital signal being low (contact made)
from either digital input as viewed by voltage level on
the digital input terminals. If neither contact has been
made (pulled input low) within the timeout period, the
valve plug will be moved to the loss-of-signal position.
Only active in the local, on-off, dual contact mode.
0=disabled.
-Continued-