Instruction Manual
D104161X012
D3 Valve with Gen 2 easy-Drive Actuator
February 2021
31
Table 4. Gen 2 easy-Drive Actuator Modbus Map (cont.)
Type Name MB Register Default R/W Values Notes
uint16 Deadband (10=1.0%) 40053 5 R/W 0-250
Minimum percentage signal change to elicit a
movement response based upon end position of last
movement. For example, if the previous command
resulted in the actuator moving to 31.2% of travel and
deadband is set to 100 (10.0%), setpoint must
command valve to 21.2% or 41.2% before valve will
move to new position. Default is set set to minimize
signal dithering.
uint16
Low travel cutoff position
(100=10.0%)
40054 50 R/W 0-999
Analog input command, in percent with one implied
decimal (50=5.0%), below this value will result in the
valve plug moving to the closed position. Active in
both local and Modbus control modes.
uint16
Analog on/off close position
(100=10.0%)
40055 400 R/W 0-999
When the valve is in 4-20mA on/off mode, this value is
the point at which the valve will close. It must be set to
a smaller value than the analog on/off open position.
Percentage position value with one implied decimal
(400=40.0%).
uint16
Analog on/off open position
(100-10.0%)
40056 500 R/W 1-1000
When the valve is in 4-20mA on/off mode, this value is
the point at which the valve will open. It must be set to
a larger value than the analog on/off close position.
Percentage position value with one implied decimal
(500=50.0%).
uint16 Analog Close Value 40057 40 R 31 - 220
The analog value, in mA with one implied decimal
(40=4.0mA), that defines the closed position
uint16 Analog Open Value 40058 200 R 31 - 220
The analog value , in mA with one implied decimal
(200=20.0mA), that defines the open position
uint16 Number of retries 40059 2 R/W 0-4
When the valve plug encounters an obstruction, how
many attempts will it make to move past that point,
assuming no change in the command signal within the
deadband range.
uint16 RESERVED 40060
uint16 RESERVED 40061
uint16 RESERVED 40062
uint16 RESERVED 40063
uint16 RESERVED 40064
uint16 RESERVED 40065
uint16 RESERVED 40066
uint16 Control Source 40067 0 R/W 0-5
0=Dual Contact On/Off 1=Single Contact On/Off,
2=Modbus On/Off, 3=Modbus Positioning, 4=4-20
Positioning, 5=4-20 Level
uint16 Valve Type 40068 1 R/W 1-10 1=D3, 2=D4
uint16 RESERVED 40069
uint16 RESERVED 40070
uint16 RESERVED 40071
uint16 RESERVED 40072
uint16 RESERVED 40073
uint16 Modbus address 40074 1 R/W 1-247 Slave Address of the actuator
uint16 Baud Rate 40075 5 R/W 4,5,6,7
4=4800 baud, 5=9600 baud (default), 6=19200 baud,
7=38400 baud
uint16 Parity 40076 0 R/W 0,1,2 0=Even, 1=Odd, 2=None
uint16 Modbus stop bits 40077 1 R/W 0,1,2
1 stop bit is the standard with even and odd parity
while 2 stop bits is the standard for none.
uint16 MSB/LSB 40078 0 R/W 0,1 0=MSB (Big Endian), 1=LSB (Little Endian)
-Continued-