GFK-2573AD May 2023
9
Release History
Version
Firmware
Revision
Date
Comments
IC695PNC001-BFBE
3.25
May 2023
PACSystems RX3i PROFINET Controller (PNC) Release
3.25 adds support for MRP Fiber SFP Ring break
detection during a single fiber break. It also resolves the
issues found in Problems Resolved in this Release.
IC695PNC001-BFBE
3.21
Aug 2022
Manufacturing component issues.
IC695PNC001-BEBD
3.20
July 2022
Support for IC695CMM002 and IC695CMM004 MODBUS
master and slave serial communications to the RX3i
PROFINET scanners IC695PNS001-Bxxx, IC695PNS101,
and IC695CEP001
IC695PNC001-BEBD
IC695PNC001CA-
BEBD
IC695PNC001LT-BEBD
3.16
Nov 2021
The product's labels have been updated to show
compliance with new certifications.
For updated certifications, please refer to
https://emerson-
mas.my.site.com/communities/en_US/Article/Certificatio
ns-and-Agency-Approvals-Landing-Page.
IC695PNC001-BDBD
3.16
Sep 2020
Manufacturing update. No change to fit, form, or
function.
IC695PNC001-BCBD
3.16
Aug 2020
Resolved a Loss of Device in an MRP Ring after the
PNC001-Bxxx is reset.
IC695PNC001-BCBD
22
3.15
Oct 2019
Rebranded the PNC001 to Emerson, applied patches for
VxWorks URGENT/11 vulnerabilities, and made
additional updates to enhance cyber security.
IC695PNC001-BBBC
3.11
May 2019
Resolves an issue sending COMMREQs to the
IC695GCG001 Genius Communication Gateway if its
PROFINET Device ID is 128 or greater.
IC695PNC001-BBBB
3.10
Nov 2018
Hardware change: slight housing dimension change to
address the issue of difficulty installing a module into a
slot with another module already installed in the left
adjacent slot.
IC695PNC001-BABB
3.10
Oct 2018
Corrects these issues: PROFINET IO Not Scanned After
Loss of Both Critical Ring Ports, Addition of IO Module
Causes IO Device to Disconnect, and Bumpless IO Using
Link Change Detection May Fail Using a PNC001-Bxxx as
an MRM. Also includes updates to enhance cyber
security.
IC695PNC001-BABA
3.00
Feb 2018
Redesign hardware and firmware for component
obsolescence, reduce power requirements, and comply
with EU RoHS.

Other manuals for Emerson PACSystems RX3i