GFK-2573AD May 2023
2
Specifications: PNC001
Specifications
Descriptions
PROFINET Support
PROFINET Version 2.2 General Class A I/O-Controller.
Redundantly controlled operation conforms to PROFINET V2.3 Type S-2 System
Redundancy.
RX3i CPU Compatibility
See the Functional Compatibility section.
Power Requirements
PNC001-Ax
PNC001-Bxxx
3.3 Vdc: 0.6 A with no SFP devices
1.3 A maximum
(two SFP devices installed, 0.35 A per SFP device)
3.3 Vdc: 0.5 A with no SFP
devices
1.2 A maximum
(two SFP devices installed,
0.35 A per SFP device)
5 Vdc: 1.5 A maximum
5 Vdc: 0.75 A maximum
Operating Temperature Range
PNC001-Ax: 0°C to 60°C PNC001-Bxxx: -25°C to 60°C
Maximum surrounding air temperature without a fan. A lower maximum
temperature may be required depending on the PNC001 location and SFP
population. Refer to the section, Operating Range for Surrounding Air Temperature
(section 1.4) in PACSystems RX3i PROFINET I/O Controller Manual, GFK-2571K or later.
Number of Port Connectors
Two RJ-45 and two SFP Cages
(SFP devices not included, available separately)
Micro USB Connector
One, is for communication with a computer using Command Line Interface.
LAN
IEEE 802.2 Logical Link Control Class I
IEEE 802.3 CSMA/CD Medium Access Control 10/100/1000 Mbps
Maximum I/O Memory
128 Kbytes of combined input/output memory per PROFINET Controller
CPU Status Bits
32
PROFINET I/O Device Data Update
Rates on the PROFINET LAN
Configurable: 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms, 64 ms, 128 ms, 256 ms, and
512 ms
Number of IP addresses
One
Number of MAC Addresses
Five. One per external port and one internal.
Hot-swappable
Yes
System Maximum Limits
PNCs per RX3i CPU
Four. Must be located in the main rack. Cannot be located in a remote node.
I/O-Devices per I/O-Controller
128 per PROFINET Controller (Configured as an MRP Manager, the PNC001 is
limited to managing no more than 63 MRP Clients).
I/O-Devices per Network
255 per network, spread across up to 8 IO-Controllers
I/O-Devices per RX3i CPU
255 per RX3i CPU, spread across up to 4 PROFINET Controllers
I/O-Controllers per network
8
Number of PROFINET Slots per
device
256
Number of PROFINET Subslots per
slot
256