GFK-2573AB Jul 2022
2
Specifications: PNC001
Specifications
Descriptions
PROFINET Support
PROFINET Version 2.2 General Class A I/O-Controller.
Redundantly controlled operation conforms to PROFINET V2.3 Type
S-2 System Redundancy.
RX3i CPU Compatibility
See the Functional Compatibility section.
Power Requirements
PNC001-Ax
PNC001-Bxxx
3.3 Vdc: 0.6 A with no SFP devices
1.3 A maximum
(two SFP devices
installed, 0.35 A per
SFP device)
3.3 Vdc: 0.5 A with no SFP devices
1.2 A maximum
(two SFP devices
installed, 0.35 A per
SFP device)
5 Vdc: 1.5 A maximum
5 Vdc: 0.75 A maximum
Operating Temperature Range
PNC001-Ax: 0°C to 60°C PNC001-Bxxx: -25°C to 60°C
Maximum surrounding air temperature without a fan. A lower
maximum temperature may be required depending on the PNC001
location and SFP population. Refer to the section, Operating Range for
Surrounding Air Temperature (section 1.4) in PACSystems RX3i PROFINET
I/O Controller Manual, GFK-2571K or later.
Number of Port Connectors
Two RJ-45 and two SFP Cages
(SFP devices not included, available separately)
Micro USB Connector
One, is for communication with a computer using Command Line
Interface.
LAN
IEEE 802.2 Logical Link Control Class I
IEEE 802.3 CSMA/CD Medium Access Control 10/100/1000 Mbps
Maximum I/O Memory
128 Kbytes of combined input/output memory per PROFINET
Controller
CPU Status Bits
32
PROFINET I/O Device Data Update Rates on
the PROFINET LAN
Configurable: 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms, 64 ms, 128 ms,
256 ms, and 512 ms
Number of IP addresses
One
Number of MAC Addresses
Five. One per external port and one internal.
System Maximum Limits
PNCs per RX3i CPU
Four. Must be located in the main rack. Cannot be located in a remote
node.
I/O-Devices per I/O-Controller
128 per PROFINET Controller (Configured as an MRP Manager, the
PNC001 is limited to managing no more than 63 MRP Clients).
I/O-Devices per Network
255 per network, spread across up to 8 IO-Controllers
I/O-Devices per RX3i CPU
255 per RX3i CPU, spread across up to 4 PROFINET Controllers
I/O-Controllers per network
8
Number of PROFINET Slots per device
256
Number of PROFINET Subslots per slot
256
Number of PROFINET Submodules per
RX3i CPU
2048