Loading...
GFK-2573AB Jul 2022
10
Upgrades
Upgrade Kit: 41G2472-FW01-000-A5
Only IC695PNC001-Bxxx or later revision modules are field upgradable to this release using the upgrade kit listed
above. IC695PNC001-Ax modules cannot be upgraded with this kit due to hardware and firmware design changes in
the PNC001-Bxxx revision.
Applications using the IC695CPE302, CPE305, CPE310, or CPE330 Version 10.05 (or later) with a PNC001-Bxxx must
also upgrade the PNC to Version 3.16 (or later) for compatibility with the CPE3xx controller.
Release in line with software license compliance requirements.
New Features and Enhancements
Subject
Description
Support for
IC695CMM002/004 in
IC695PNS001-Bxxx,
IC695PNS101, and
IC695CEP001 devices
The handling of the MODBUS Master and Slave data between the CPU and the CMM
modules requires changes available in R3.20 when using an IC695PNC001-Bxxx module
as the PROFINET IO Controller.
Problems Resolved in this Release
Issue
ID Code
Description
Cyber Security
Updates
DE7177,
DE6997,
DE6632,
DE8516
Added security enhancements to harden the product against a malicious
actor.
No LEDs on After
Power Cycle or
Firmware Update
DE6793
Quick power cycles or restart after a firmware update could cause the module
to stall during boot with no LEDs turned on. A cold powerup was necessary for
restoration. This issue has been fixed. The first time the module powers on
with firmware containing the fix, it updates an internal component and
restarts a second time to full operation.
Explore PROFINET
Networks Does Not
Show VFD
Information
DE7499
Explore PROFINET Networks does not display detail for a VFD lower in the
tree-view than the VFD name level. This issue is corrected.